53
•
Make sure the PV array is well insulated to ground before connecting it to the
inverter.
•
Make sure the maximum DC voltage and the maximum short circuit current of
any string never exceed inverter permitted values specified in "Technical Data".
•
Check the positive and negative polarity of the PV strings, and connect the PV
connectors to corresponding terminals only after ensuring polarity correctness.
•
During the installation and operation of the inverter, please ensure that the posi-
tive or negative electrodes of PV strings do not short-circuit to the ground. Oth-
erwise, an AC or DC short-circuit may occur, resulting in equipment damage.
The damage caused by this is not covered by the warranty.
•
Electric arc or contactor over-temperature may occur if the PV connectors are
not firmly in place, and SUNGROW shall not be held liable for any damage
caused.
•
If the DC input cables are reversely connected or the positive and negative ter-
minals of different MPPT are shorted to ground at the same time, while the DC
switch is in the "ON" position, do not operate immediately. Otherwise, the inver-
ter may be damaged. Please turn the DC switch to "OFF" and remove the DC
connector to adjust the polarity of the strings when the string current is lower
than 0.5 A.
Before connecting the PV array to the inverter, ensure that the impedances be-
tween the positive terminals of the PV string and earth, and between the negative
terminals of the PV string and earth are larger than 1 M Ohm.
The following requirements about PV string connection must be met. Otherwise, it
may cause irreversible damage to the inverter, which is not covered by the
warranty.
•
Mixed use of different brand or model of PV modules in one MPPT circuit, or PV
modules of different orientation or angles in a string may not damage inverter
but will cause system bad performance!
6.6.1 PV Input Configuration
In Australia and New Zealand, ensure the DC power for any PV string never exceeds a cer-
tain level with regards to the string voltage to avoid derating:
≤ 12.5 kW if string voltage is lower than 500 V
≤ 10 kW if string voltage is between 500 V and 800 V
≤ 8 kW if string voltage is between 800 V and 1000 V