92
figure 7-15
Q(P) Curve
“Q(U)” Mode
table 7-10 “Q(U)” Mode Parameter Descriptions:
Parameter
Explanation
Range
Reactive response
Switch for enabling/disabling reactive
response
Enable/Disable
Reactive response
time
Completion time of reactive response
0.1s~600.0s
Q(U) curve
Select corresponding curve according to lo-
cal regulations
A, B, C
*
Hysteresis Ratio
Voltage hysteresis ratio on the Q(U) mode
curve
0 ~ 5%
QU_V1
Grid voltage limit at P1 on the Q(U) mode
curve
80% ~ 100%
QU_Q1
Value of Q/Sn at P1 on the Q(U) mode
curve
[-60.0%-0]* Over-
load Rate/ 1000
QU_V2
Grid voltage limit at P2 on the Q(U) mode
curve
80% ~ 100%
QU_Q2
Value of Q/Sn at P2 on the Q(U) mode
curve
[-60.0%-60.0%]*
Overload Rate/
1000
QU_V3
Grid voltage limit at P3 on the Q(U) mode
curve
100% ~ 120%
QU_Q3
Value of Q/Sn at P3 on the Q(U) mode
curve
[-60.0%-60.0%]*
Overload Rate/
1000
QU_V4
Grid voltage limit at P4 on the Q(U) mode
curve
100% ~ 120%
QU_Q4
Value of Q/Sn at P4 on the Q(U) mode
curve
[0-60.0%]* Over-
load Rate/ 1000
QU_EnterPower
Active power for Q(U) function activation
20% ~ 100%