114
Parameters
SG320HX
SG350HX
AC connection type
Support OT/DT terminal
(Max. 400 mm²)
Support OT/DT terminal
(Max. 400 mm²/ 789 Kcmil)
Grid Support
Q at night function, LVRT,
HVRT,active & reactive
power control and
power ramp rate control
Q at night function, LVRT,
HVRT,active & reactive
power control and power
ramp rate control, Q-U con-
trol, P-f control
*: Only compatible with Sungrow logger and iSolarCloud
10.2 Wring Distance of DI Dry Contact
The maximum wiring distance of DC dry contact must meet the requirements in the Table
below. The wiring distance L is the total length of all DI signal cables.
L
K
refers to the cable length in one direction between the DI dry contact terminal of the k
th
in-
verter and the corresponding terminal of the (k-1)
th
inverter.
table 10-1 Correspondence between number of inverters and maximum wiring distance
Number of
inverter
Maximum wiring distance(unit:m)
16AWG / 1.31mm
2
17AWG / 1.026mm
2
1
13030
10552
2
6515
5276
3
4343
3517
4
3258
2638
5
2606
2110
6
2172
1759
7
1861
1507
8
1629
1319
9
1448
1172
10
1303
1055
11
1185
959
12
1086
879
13
1002
812
14
931
754