Figure 5 Battery terminals inside the inverter 

If  the  battery  is  not  connected  properly  or  powered  off,  the  voltage  reading  on  the 

battery  terminal  inside  the  inverter  may  display  around  20V,  which  is  from  the 

inverter circuit board. 

If the LED on the battery does not display any light, it means the battery is OFF. To 

turn ON the battery, take the 

top cover off and press and hold the ‘

Red

’ button for 

seconds 

(Figure 6). 

 

Figure 6 Battery power ON/OFF button 

After pressing and holding the red button for 5 seconds, if the LED does not light up, 

disconnect  all  the  cables  from  the  battery  and  measure  the  voltage  at  the  battery 

terminals  and  check  if  the  voltage  reading  ranges 

between  44.8V  and  58.1V

.  (If 

required, switch on the battery by pressing the red button for 5 seconds). 

 

Figure 7 Voltage at the battery terminals 