background image

 

 Sungrow Australia Group Pty. Ltd. | 1800 SUNGROW (786 476)

 

[email protected]

 

www.sungrowpower.com.au

 
 

TD_201806_SBP4K8_Battery Testing_V1.0

 

Page 2 of 4

 

 

© Sungrow Australia Group Pty. Ltd. All rights reserved. 
The information in this document is subject to change without notice. 

If the LCD screen on the inverter shows ‘

--

’ on the battery side, please re-check the 

wiring (especially the data cables). If the status on the i

nverter screen shows ‘Error’, 

check the error code on the inverter menu.  

Battery Status 

Check the status of the battery via the LED light on the battery (Figure 4). 

 

Figure 4 LED light on the battery 

Table  1  below  shows  the  battery  state  and  definition  of  each  state  represented  by 

different LED colour, which can be used to check the status of the battery.  

Table 1 Battery LED colour, state and definition 

 

If the battery is connected and displays Green LED light, measure the voltage at the 

battery  terminal  inside  the  inverter  (Figure  5).  During  normal  battery  operation,  the 

voltage  at  the  battery  terminal inside  the inverter  should  range  between 

44.8V  and 

58.1V