activates when excessive temperatures are detected.  The inverter may overheat if installed in a location that 

does not allow proper ventilation and does not allow dissipation of heat.  Over heating may also occur when 

powering an appliance that exceeds the wattage ratings of the inverter.  Under normal operating conditions 

the Over Temperature LED and the Cooling Fan will turn off after fifteen minutes.  Automatically, the inverter 

will restart indicating that the inverter has reached a safe operating temperature.   

Over Load 

If the continuous power draw of the appliance(s) being operated exceeds 5000 Watts this light will turn RED 

and the inverter will shut down.  When this occurs turn off the inverter and the appliance then determine the 

cause of the overload before turning the inverter and the appliance on again on again.   

     

C. Battery Voltage and Inverter Output Wattage Bar Graph (Green Yellow and Red) 

Wattage Indicator 

The output wattage of the inverter is monitored by this illuminated display.  Depending upon the amount of 

output wattage, the bar graph reading generally will be in GREEN (safe) or YELLOW (caution).  If the level 

reaches RED (overload) the inverter may automatically shut down.   

Volts Indicator 

The voltage being drawn from the battery by the inverter is monitored by this illuminated display.  Under 

optimum conditions this reading will be in GREEN.  A low voltage draw will show a reading that is close to the 

actual voltage of the battery.  These readings are the result of measuring the voltage in both the positive and 

the negative input cables.  This inverter will operate with input voltage ranging from 10 to 15 volts DC.  If the 

voltage level falls below 10 volts DC, the voltage indicator will register in RED and an audible alarm will 

sound.  The inverter will automatically shut down and the voltage indicator display will turn off.   

The 5000 Watt Power Inverter may be damaged if the input voltage exceeds 15 volts.  The inverter will 

automatically shut down if this occurs, however despite this safety feature excessive voltage may cause 

damage to the inverter.  Damage caused by excess voltage input is not covered under warranty. 

When turning the inverter ON the voltage bar graph should show between 10 and 15 volts depending on the 

voltage of the power source.  When the voltage reading does not fall within this range, check the connection 

of the wires to terminals on the power source and on the inverter.  Also check the voltage of the power source.  

Finally, ensure the Over Temperature and Over Load LED  Indicator is not lit. 

 

D.  Four Standard North American 110V AC Outlets 

E. High Speed Cooling Fan 

When the temperature inside the inverter exceeds limits of safe operation the fan will automatically turn on to 

cool the inverter.  When the temperature has lowered to a safe operating temperature the fans will shut off 

automatically.  The fan is not designed to run continuously.  

F. Ground Terminal 

G. Positive Power Input Terminal 

H.  Negative Power Input terminal 

I.  Wireless Remote Control Accessory Socket 

The 5000 Watt Power Inverter may be controlled by remote control.  The remote control receiver must be 

plugged into the Remote Control Accessory Socket 

Notice 

While using the wireless remote control please remember to switch both the receiver and the inverter to the 

OFF position.   

In the event the remote control is lost, and you are unable to turn the inverter off, disconnect the remote 

control receiver from the Wireless Remote Control Accessory Socket and turn the inverter off on the front panel.   

 

Selecting a Power Supply 

When you operate the 5000 Watt Power Inverter for long periods of time combined with a high continuous load 

demand the result will be a large power drain from the battery.  With this in mind, check the reserve capacity of 

your battery.  In most case several batteries will be required to provide power to your inverter. 

 

1. 

When calculating the amp/hour rating find the “reserve minute”.  This is typically marked on the battery 

next to the Cranking Amps rating.  If you multiply the reserve minutes by 0.3 you will have the battery 

Amp/Hour rating.   

A battery with 150 reserve minutes has an Amp/Hour rating of 45. 

2. 

To estimate the maximum power the inverter will require to run a piece of equipment or appliance 

divide the continuous load requirement by 10.  An appliance with a 450 Watt continuous load will require a 

minimum 45 amp draw from a battery.   

3. 

A 45 Amp/hour battery (150 Reserve Minutes) will be sufficient to power this appliance for a maximum 

of one hour. 

 

Note 

  The type of battery you use to power your inverter is important.  Batteries designed to start engines have 

multiple layers of very thin plates.  These provide extensive surface area that will provide a powerful 

Содержание 5000 Watt POWER INVERTER

Страница 1: ...5000 Watt POWER INVERTER ONDULEUR DE PUISSANCE 5000 Watt INVERSOR de 5000 Watt User s Manual Notice D utilisation Manual del Usario...

Страница 2: ...FLOOD EYE WITH RUNNING COLD WATER for at least 10 minutes GET MEDICAL ATTENTION IMMEDIATELY Failure to comply with above warnings may lead to explosion and or severe injury Do not expose the inverter...

Страница 3: ...lculate most starting loads Starting Load 2 x WATTAGE In general the start up load of the appliance or power tool determines whether your inverter has the capability to power it To calculate the conti...

Страница 4: ...e of the power source When the voltage reading does not fall within this range check the connection of the wires to terminals on the power source and on the inverter Also check the voltage of the powe...

Страница 5: ...to Connect the Inverter 1 Make sure the ON OFF rocker switch see diagram part A is in the OFF 0 position 2 Connect the BLACK cable to the BLACK negative power input terminal see diagram part F of you...

Страница 6: ...hat the antenna cable is adequately shielded and of good quality 2 Try altering the positions of the inverter antenna cables and television power cord 3 Add an extension cord from the inverter to the...

Страница 7: ...conversion 5000 Watt Power Inverter The modified sine wave inverter has a root mean square RMS voltage of 110 volts but most AC voltmeters are calibrated to measure pure sine waves for their RMS volt...

Страница 8: ...ance Inverter is too hot causing thermal overload Shut off inverter to allow cooling Ensure proper ventilation Red LED on Inverter may be defective Contact tech hotline Electrical interference from th...

Страница 9: ...load Temperature Yes Short Circuit Protection Yes Physical Dimensions 16 x 8 4 x 7 8 40 5 cm x 21 3 cm x 20 cm Weight appro 23 15 lbs 10 5 kg LIMITED WARRANTY This product is covered by a one year lim...

Страница 10: ...e oxyg ne pouvant causer des explosions De plus elles contiennent de l acide sulfurique pouvant causer des br lures graves Assurez vous que l environnement dans lequel vous travaillez est bien a r NE...

Страница 11: ...eut g n rer des tincelles caus es par le courant de charge des condensateurs internes de l onduleur Ceci est normal Consid rant ce risque d tincelles il est extr mement important que l onduleur et la...

Страница 12: ...peut tre tr s dangereuse L utilisation incorrecte de votre onduleur peut r sulter en des dommages mat riaux des blessures personnelles et mortelles A Interrupteur bascule ON OFF MARCHE ARR T B C Voya...

Страница 13: ...nsion de la source d alimentation Finalement assurez vous que le voyant DEL Over Temperature Surchauffe et Over Load Surcharge n est pas allum D Quatre prises de courant de 110 VCA ordinaires Am rique...

Страница 14: ...la source de 12 volts Lorsqu une rallonge est utilis e entre l onduleur et un appareil assurez vous qu elle n exc de pas 50 pieds 15 2 m tres cette distance le risque de chute de tension est limit Ca...

Страница 15: ...ut r sulter en un incendie ou une explosion Mise la masse de l onduleur Localisez la borne de mise la masse de l onduleur Acheminez un fil de calibre 0 de la borne de la mise la masse un point de mass...

Страница 16: ...ternes exc de 165 F 74 C Attention L onduleur de puissance de 5 000 watts est quip d un ventilateur Si le ventilateur est incapable de maintenir la temp rature un niveau qui assure un fonctionnement s...

Страница 17: ...que l onduleur n est pas pr s de sources potentielles de vapeurs ou de gaz inflammables avant de raccorder l onduleur la source d nergie Assurez vous que la consommation lectrique de l appareil ou de...

Страница 18: ...l viseur Interf rence avec le t l viseur Le signal de la t l vision est trop faible Essayez un autre t l viseur Diff rentes marques et mod les op rent diff remment lorsque des interf rences existent T...

Страница 19: ...Dimensions 16 x 8 4 x 7 8 40 6 x 21 3 x 19 8 cm Poids Environ 23 15 lb 10 5 kg GARANTIE LIMIT E Ce produit est couvert par une garantie limit e d un an Sunforce Products Inc garantit l acheteur initi...

Страница 20: ...AL MEDICO INMEDIATAMENTE El no seguir las precauciones anteriores puede provocar una explosi n o da os muy importantes No exponga el inversor a humedad incluyendo lluvia nieve roc o o humedad excesiv...

Страница 21: ...apacidad de suministrar suficiente energ a Para calcular la carga continua igual que el vataje en la f rmula de m s arriba Carga continua A amperios x 110 tensi n CA Atenci n Realice siempre una prueb...

Страница 22: ...l inversor Da os causados por exceso de tensi n no est n cubiertos por la garant a Cuando encienda el inversor ON el gr fico de tensi n muestra entre 10 y 15 V dependiendo de la tensi n de la fuente d...

Страница 23: ...tilizar un cable de extensi n desde el inversor aseg rese que el cable de extensi n no es m s largo que 50 pies 15 m No deber a de haber riesgo de p rdida de energ a con esta longitud Di metro de los...

Страница 24: ...esta conexi n a Tierra tirando el cable a un suelo de tierra Antes de conectar la tierra aseg rese que el inversor est apagado Hacer funcionar el inversor sin conexi n adecuada a tierra puede provoca...

Страница 25: ...funcionar o cualquier otra superficie que pueda estar en contacto con cualquier fuente de energ a est n mojados El agua y muchos otros l quidos pueden ser conductores de electricidad lo que puede pro...

Страница 26: ...o en marcha durante aprox 20 minutos para recargar la bater a Si oye una alarma continua o apagado autom tico i Apague inmediatamente el inversor ii No vuelva a arrancar el inversor hasta que el orige...

Страница 27: ...no experimentar las mismas interferencias Tensi n de entrada inferior a 10 V Recargue o sustituya la bater a Puede que sea necesario el uso de dos bater as para hacer funcionar algunos aparatos Alarma...

Страница 28: ...tada Sunforce Products Inc garantiza al comprador original que este producto est libre de defectos de funcionamiento y de defectos en materiales y mano de obra durante un per odo de una a o a partir d...

Страница 29: ......

Отзывы: