Site Planning Guide for Sun Blade 6000 and Sun Blade 6048 Modular Systems • February 2012
Thermal Design Specifications
The thermal design specifications of the system are shown in the following table.
Acoustic Noise Emissions
Declared noise emissions are in accordance with ISO 9295/9296 standards.
Data center personnel should take necessary precautions to reduce exposure to the
high noise levels. Acoustic noise emission levels are shown in the following table.
Relative humidity (RH)
10 to 90% RH,
noncondensing,
27
o
C max wet bulb
5 to 93% RH,
noncondensing,
38
o
C max wet bulb
Optimum ambient relative
humidity
45 to 50% RH,
noncondensing
Altitude
0 to 10,000 feet (3048 m)
maximum ambient
temperature is derated by
1
o
C per 300 m (984 ft)
above 900 m (2953 ft)
0 to 39,370 feet
(12,000 m)
Sine vibration
Operating: Z (vertical)
axis: 0.15 G, X-Y axis: 0.10
G, 5 Hz-500 Hz sine
Z (vertical) axis: 0.50 G,
X-Y axis: 0.25 G, 5
Hz-500 Hz sine
Shock
3 Gs, 11 msec, half sine
(rackmounted enclosure)
Parameter
Specification
Maximum possible system volumetric airflow
1012 CFM
Maximum possible heat dissipation/HVAC load
21,325 BTU/hr
Maximum possible temperature rise through chassis
18.5
o
C (33
o
F)
Specification
Operating
Nonoperating