Chapter 2
Troubleshooting
15
TABLE 2-2
LED Indicators on the Power Sequencer
Condition
LED
LED Status
Troubleshooting Action
Normal operation
Okay to Remove
OFF
No action required.
Fault
OFF
Ready
ON
~ AC 1-9 ODD
ON
~ AC 0-8 EVEN
ON
Sequencer fault
Okay to Remove
OFF
1. Turn off both power switches. The blue
“Okay to Remove” LED lights.
2. Remove and replace the power sequencer.
Fault
ON
Ready
(ON or OFF)
~ AC 1-9 ODD
ON
~ AC 0-8 EVEN
ON
Turned off
Okay to Remove
ON
You can safely remove the sequencer.
Fault
(ON or OFF)
Ready
(ON or OFF)
~ AC 1-9 ODD
OFF
~ AC 0-8 EVEN
OFF
Missing AC input
Okay to Remove
OFF
Assuming both power switches are on, start
troubleshooting the input to the sequencer:
1. Input power panel connectors
2. Branch (wall) circuit breaker
Fault
OFF
Ready
ON
~ AC 1-9 ODD
OFF
~ AC 0-8 EVEN
ON