Sun Blade

8000 Series

Site Planning Guide

Part No. 819-5648-15
February 2008  Rev A

Содержание Blade 8000 Series

Страница 1: ...Sun Microsystems Inc www sun com Submit comments about this document at http www sun com hwdocs feedback Sun Blade 8000 Series Site Planning Guide Part No 819 5648 15 February 2008 Rev A...

Страница 2: ...D EXCEPT TO THE EXTENT THAT SUCH DISCLAIMERS ARE HELD TO BE LEGALLY INVALID Copyright 2008 Sun Microsystems Inc 4150 Network Circle Santa Clara Californie 95054 tats Unis Tous droits r serv s Sun Micr...

Страница 3: ...or the Sun Blade 8000 Series Systems 1 Customer Obligations 1 System Configuration 2 Preparing the Site Before the System Arrives 2 Load Bearing and Handling Precautions 3 Power and Electrical Require...

Страница 4: ...nt of a Sun Product 10 Hazardous Conditions Precautions 10 System Specifications 11 Shipping Crate Physical Specifications 12 Chassis and Components Dimensions and Weights 12 Environmental Specificati...

Страница 5: ...This document is written for data center administrators who have advanced experience maintaining a data center environment and for experienced system installers Sun Blade 8000 Series Product Web Sites...

Страница 6: ...ntent Title Part Number Format Location Late breaking information Sun Blade 8000 Series Product Notes 819 5651 PDF HTML Web Site Planning this document Sun Blade 8000 Series Site Planning Guide 819 56...

Страница 7: ...ggestions You can submit your comments by going to http www sun com hwdocs feedback Please include the title and part number of your document with your feedback Sun Blade 8000 Series Site Planning Gui...

Страница 8: ...viii Sun Blade 8000 Series Site Planning Guide February 2008...

Страница 9: ...ganized as follows Customer Obligations on page 1 System Configuration on page 2 Preparing the Site Before the System Arrives on page 2 Compatible Cabinets on page 8 Route to the Data Center on page 9...

Страница 10: ...tem consists of the following hardware components 14U chassis Sun Blade 8000 P Chassis Up to 10 Sun Blade Server Modules Up to 2 Chassis Monitoring Modules CMM Up to 2 Network Express Modules NEM 4 po...

Страница 11: ...lade 8000 P Chassis uses four power supply modules In both chassis the modules provide 48V at 3000W per supply for a total of 9000W per chassis The AC power requirements for the Sun Blade 8000 Series...

Страница 12: ...e loss of either AC feed The Sun Blade 8000 P Modular System supports N 1 power supply redundancy A minimum of three operating power supplies are required to support a fully configured system without...

Страница 13: ...wer Calculators to help you determine the power requirements of either the Sun Blade 8000 or Sun Blade 8000 P Modular System The intent of the Power Calculator is to provide guidance for estimating th...

Страница 14: ...systems are provided in TABLE 9 Temperature and Humidity Requirements Avoid temperature and humidity extremes The operating and nonoperating temperature specifications listed in TABLE 7 reflect the sy...

Страница 15: ...ntilation areas of the chassis Ensure that all cabling at the rear of the chassis does not block any exhaust air Ensure that front and rear cabinet doors are at least 60 perforated to ensure minimal r...

Страница 16: ...nto the rack but also the rack units taken up by the power distribution system s being used in the rack Determining the power requirements is more complex to calculate especially if you plan to power...

Страница 17: ...idity difference between the system and the data center environment keep the system in its shipping container in a location that has a temperature and humidity environment similar to the data center W...

Страница 18: ...stem Never place a Sun product near a radiator or heat register Failure to follow these guidelines can cause overheating and affect the reliability of your Sun product Air cools the Sun Blade 8000 Ser...

Страница 19: ...er panels 1 CMM filler panel and 4 Network Express Module filler panels The standard Sun Blade 8000 P Modular System is shipped with the following components installed 1 Sun Blade 8000 PChassis 4 powe...

Страница 20: ...allet weight Approximately 600 lb 272 kg Approximately 484 lb 220 kg TABLE 5 Chassis and Component Physical Specifications Sun Blade 8000 System Dimension or Weight Specification Chassis height 33 01...

Страница 21: ...hassis handles 20 lb 9 07 kg I O chassis with midplane 15 lb 6 80 kg Power supply module 9 25 lb 4 19 kg Server Module 23 lb 10 43 kg Rear fan module 3 lb 1 36 kg Network Express Module 7 lb 3 18 kg T...

Страница 22: ...in rack with modular power system IEC320 C319 to IEC320 C20 1 5 m Sun PN X5046A Z 2 0 m Sun PNX5047A Z Sun Blade 8000 P Chassis Americas Domestic NEMA L6 20P to IEC320 C19 4 m Sun PN X5074A Z Internat...

Страница 23: ...th ISO 9295 9296 standards TABLE 10 Chassis Airflow Specifications Sun Blade 8000 and 8000 P Systems Function Specification Airflow 1500 cfm Airflow direction Front to back TABLE 11 Acoustic Noise Spe...

Страница 24: ...and fans rated 27V or greater system is exempt since it is rated gretaer than 1300W CE Declaration of Conformance SMI self declaratin to The Electronic Compatibility Directive and Low Voltage Directi...

Страница 25: ...ient burst immunity test IEC 61000 4 5 Surge immunity test IEC 61000 4 6 Immunity to conducted disturbances induced by radio frequency fields IEC61000 4 8 Power frequency magnetic field immunity test...

Страница 26: ...u maintain the data center environment when certain failures occur such as power failure air conditioning unit failure or humidity control unit failure Yes__ No__ Is fire suppression and alarm equipme...

Страница 27: ...enter the air inlet of another system Yes__ No__ Is there sufficient room around the racks for system access and maintenance Miscellaneous Yes__ No__ Are there sufficient number of people available to...

Страница 28: ...20 Sun Blade 8000 Series Site Planning Guide February 2008...