4. SELECTING A LOCATION
Typically the HRV is located in the mechanical room with close
proximity to an outside wall. Other installation locations are
acceptable provided that the ambient air temperature does not
fall below freezing. This is to prevent the condensate drain lines
from freezing.
5. MOUNTING THE HRV
The ProVentor series of HRVs may be rotated 180 degrees to permit the connection of the
outside air streams to either the left or right hand side. They are factory supplied to be
nstalled with the cold air support streams on the left. To install this HRV in the reverse
configuration simply remove the plastic drain hole plugs from the top of the cabinet and insert
into the drain holes in the bottom.
Included with the HRV are four (4) laminated rubber hanging straps. These are to be secured
at each of the four corners of the HRV using the screws provided. The other ends of the straps
should be secured to the floor joists using large head screws. To ensure proper condensate
flow, HRV must be installed level in both directions.
NOTE: The cold supply duct collar is supplied loose. Once the orientation of the HRV is
determined, install this collar using the four screws provided. This collar must be installed
with its orientation arrows on the side of the collar pointing up.
HRV duct connections are 6”