background image

This installation must conform with the requirements of the authority having jurisdiction 

or in the absence of such requirements with the latest edition of the National Fuel 

Gas Code ANSI Z223.1/NFPA 54; and the latest edition of the American National 

Standard for Recreational Vehicles NFPA 1192.

In Canada

, the installation should conform with the following standards:

A.  For installation in Recreational Vehicle

 1. 

Gas - CSA standard CSA Z240.4.2-08 Installation Requirements for Propane 

Appliances and Equipment in Recreations Vehicles.

 2.

  Electrical  -  CSA  standard  C22.2  No.  148/Z240.6.2-08/C22.2  No.  148-08 

Electrical Requirements for Recreational Vehicles.

 3. 

Plumbing  -  CSA  standard  CSA  Z240.3.2  Plumbing  Requirements  for 

Recreational Vehicles.

B.

  The appliance shall be disconnected from the gas supply piping system during 

any pressure testing of the system.

C.

  The appliance and its gas connections shall be leak tested before placing the 

appliance in operation.

D.

  All  air  for  combustion  must  be  supplied  from  outside  the  structure.  Air  for 

combustion must not be supplied from occupied spaces.

E.

  Minimum clearance from combustible construction on sides and top - 1/4 inches. 

Provide room for access to rear of heater and at left side for servicing.

F.

  Choose a location for installation out of the way of wires, pipes, etc. that might 

interfere with the installation.

G.

  When an appliance is installed directly on carpeting, tile or other combustible 

material, other than wood flooring, the appliance shall be installed on a metal 

or wood panel the full depth of the appliance. If preferred the carpeting, tile or 

combustibles materials, other than wood may be cut away the full length of the 

appliance plus the appliance minimum clearances to combustibles.

H. 

Good grounding of the unit is recommended to mitigate static charge built up by 

attaching a 12 gage ground wire to the unit case at the green grounding screw 

shown in 

Figure 5 

and securely fasten the ground wire to the RV metal frame.

I. 

Do not install the water heater with the vent facing toward the forward end of the 

coach. 

See Figures 1, 2 and 3.

J.

  There must be access for removing unit for service.

INSTALLATION WITHOUT REPLACEMENT PANEL

1.

  Locate area for installation of the unit. The unit should be installed as close to wall 

as possible. Mark wall as shown in 

Figure 4

 and cut a 3.750" Diameter hole for vent 

installation.  On mesa or yoder type side walls, it may be required to flatten area 

where vent is to be installed to assure seal around vent assembly. 

2.

  Place unit on floor (verify vent cap lines up with exhaust tube and combustion air 

opening in unit).

 

a.

  Drain lines must be connected to the system and condensation drains on 

the On Demand water heater and ran to the outside of the RV.  Drain Lines 

should be as short as possible and must maintain a drop of ¼” per foot from 

unit.  See 

Figure 5

.

3.

  Install vent assembly. See 

Figure 6

 

a.

  Vent cap must be ordered separately.  See 

TABLE 1

 for vent sizes and part 

numbers.  A minimum overlap of 1.25" is required on exhaust.

 

b.

  Apply a bead of silicone around the vent cap as shown in 

Figure 6

.

 

c.

  Install vent cap as shown in 

Figure 6

 with screws.  Insure assembly is sealed 

to outside wall to prevent leaks.

4.

  Screw the front of the unit to the floor using the two brackets as shown in 

Figure 5

.  If 

necessary, the brackets can be moved to the rear of the unit as shown in 

Figure 7B.

5.

  Make gas, water and electrical connections following instructions contained in 

this manual supplied with the Suburban NAUTILUS (IW60) On Demand Water 

Heater.

INSTALLATION USING REPLACEMENT PANEL

A replacement panel is used when replacing Suburban 6, 10, 12, and 16 gallon tank 

units and Atwood Style 6 and 10 gallon tank units.

1. 

On mesa or yoder type sidewalls, flatten the wall area around the opening.

2.

  Apply a continuous line of suitable caulk on the RV wall around all four sides 

of the opening and around back side of replacement panel frame as shown in 

Figure 8

. Required to create water tight seal of the frame to the RV wall.

3.

  Center and insert caulked replacement panel frame into opening.  Push frame 

firmly against RV wall over caulking previously applied in step 2.  Secure frame 

with the eight (8) supplied screws into RV wall as shown in 

Figure 8

.

4.

  Locate  the  water  heater  cabinet  approximately  even  with  the  inside  RV  wall.  

See

 Figure 7B

.    If  securing  the  unit  to  the  floor  using  the  FRONT  mounting 

brackets,  proceed  to  STEP  5.    To  mount  the  water  heater  using  the  REAR 

mounting method, remove the two mounting brackets from the front of the unit 

and secure them to the threaded holes at the rear of the unit.  Screw the rear of 

the unit to the floor using the two brackets. See 

Figure 7B

.

5.

  Using the gasket supplied with the kit, apply the gasket beginning at the center 

bottom of the replacement panel frame.  Adhere the adhesive side of the gasket 

to the replacement panel frame and install the gasket all the way around the 

frame.  Insure the ends of the gasket meet at the center bottom of the access 

panel frame.

6.

  Attach the replacement panel to the frame as shown in 

Figure 8

 using the five 

(5) screws provided.

7.

  Vent cap must be ordered separately.  See 

Table 1

 for vent sizes and part numbers. 

There must be a minimum of 1.25" (31.8mm) overlap of vent assembly tube over 

exhaust tube on the On Demand Water Heater and the replacement panel must 

compress the replacement panel gasket.  See 

Figure 7A

.

 

a.  Apply a bead of silicone around the vent cap as shown in 

Figure 8

.

 

b.  Install vent cap as shown in 

Figure 8

 with four (4) screws.  Insure assembly 

is sealed to outside wall to prevent leaks.

8.

  Screw the front of the unit to the floor using the two brackets as shown in 

Figure 5

.

9.

  Apply  silicone  caulk  around  the  beveled  edges  of  the  replacement  panel  as 

shown in 

Figure 8

.  Do not caulk the bottom of the replacement panel.

10.

  Make gas, water and electrical connections following instructions contained in this 

manual supplied with the Suburban Nautiluis IW60 On Demand Water Heater.

11.

  Drain lines must be connected to the system and condensation drains on the On 

Demand Water Heater and ran to the outside of the RV.  Drain Lines should be 

as short as possible and must maintain a minimum drop of ¼” per foot. (6.4mm 

per 305mm) from unit.  See 

Figure 5

.

ACCESS PANEL PART NUMBERS

BRAND

CAPACITIES

PART NUMBER

SUBURBAN

6 GALLON

6276APW (Polar White)

SUBURBAN

10, 12, 16 GALLONS

6277APW (Polar White)

ATWOOD

6 GALLON

521147 (Polar White)

ATWOOD

10 GALLON

521150 (Polar White)

VENT CAP PART 

NUMBER

VENT CAP 

LENGTH

"X" MAX DIMENSION

260616

0 - 1  inches

1.171 inch

260617

1 - 2 inches

2.171 inch

260618

2 - 3 inches

3.171 inch

260638

5 - 6 inches

6.171 inch

TABLE 1

MAKING ELECTRICAL CONNECTIONS

12 VOLTS D.C.

A. 

The electrical connections must be made in accordance with local codes and 

regulations. In the absence of local codes and regulations, refer to the latest 

edition of the National Electrical Code NFPA 70.

In Canada

, the electrical installation should conform with CSA standard  Z240.6.2-

08/C22.2 No. 148-08 Electrical Requirements for Recreational Vehicles.

B.

  Make  the  12  Volt  D.C.  electrical  connections  following  the  wiring  diagram 

illustrated in 

Figure 11

.

If  the  power  supply  is  to  be  from  a  convertor,  we  recommend  that  the  converter 

system be wired in parallel with the battery. This will serve two purposes:

 

1.

  Provide a constant voltage supply

 

2.

  Filter any A.C. spikes or volt surges

We recommend insulated terminals be used for all electrical connections.

INSTALLATION OF SWITCH AND LIGHT 

ASSEMBLY 

(SEE FIGURE 12)

1.

  ON/OFF switch is wired as shown in wiring diagram.  See 

Figure 11

.

2. 

There is a connection for a lockout light.  (If used, this light will come on if the unit 

goes into lockout.  Water must be turned off and back on to re-cycle the unit.)

3. 

Connect ORANGE wire to LED lamp (+) and BLUE wire to LED lamp (-).

INSTALLATION OF OPTIONAL ON DEMAND 

CONTROL CENTER 

(SEE FIGURE 13)

 WARNING

Do  not  use  on  circuits  exceeding  specified  voltage.  

Higher  voltage  will  damage  control  center  and  could 

cause shock or fire hazard.  Do not short out terminals 

on gas valve or primary control to test.  Short or incorrect 

wiring will damage thermostat and could cause personal 

injury and/or property damage.

1.

  On Demand Control Center is wired as shown in wiring diagram.  See 

Figure 11

.

2. 

Locate the On Demand CONTROL CENTER on a wall surface adjacent to the 

On Demand water heater.

3.

  Remove back cover from control center by depressing latch at bottom.

4.

  Remove  center  knockout  from  back  cover.    Drill  hole  for  wiring  from  control 

center.  See 

Figure 14.

5.

  Mount back cover to the wall.

6.

  Route wiring through back cover and hole into wall.

7.

  Connect the two white wires from the On Demand Control Center to the two 

white wires from the On Demand water heater.  See 

Figure 11

.

The optional On Demand CONTROL CENTER displays the water temperature and 

also allows outlet water temperature to be adjusted (130°F maximum).

ON DEMAND CONTROL CENTER

PART NUMBER

BLACK

161253

WHITE

161252

MAKING DRAIN CONNECTIONS

A.

 

Drain connections are made at the front of the water heater.  Refer to 

Figure 5

.  

Connect 5/8” ID hose to system drain fitting provided on front of unit.  Connect 

½” ID hose to condensation drain fitting provided on front of unit.

B.

  Drain lines must run to the outside of the RV.  Drain lines should be as short as 

possible and must maintain a minimum drop of ¼” per foot. (6.4mm per 305mm).  

See 

Figure 5

.

MAKING WATER CONNECTIONS

A. 

Water connections are made at the front of the water heater. Refer to 

Figure 5

.  

Connect the hot and cold water lines to the 1/2” NPT female pipe fitting provided 

on front of unit. These fittings are marked “HOT” and “COLD”.

3

Содержание NAUTILUS IW60

Страница 1: ...ODORANT IS ADDED TO THE GAS USED BY THIS WATER HEATER INSTALLER AFFIX THESE INSTRUCTIONS TO OR ADJACENT TO WATER HEATER OWNER RETAIN THESE INSTRUCTIONS AND WARRANTY FOR FUTURE REFERENCE ALL TECHNICAL...

Страница 2: ...ly to the appliance Do not install this appliance to where the vent terminates below a slide out This appliance is not to be installed under any overhang It must be free and clear of any type overhang...

Страница 3: ...ket supplied with the kit apply the gasket beginning at the center bottom of the replacement panel frame Adhere the adhesive side of the gasket to the replacement panel frame and install the gasket al...

Страница 4: ...th the door open OPERATING INSTRUCTIONS WITH SWITCH AND LIGHT ASSEMBLY 1 STOP Read the safety information above 2 Turn off all electric power to the appliance 3 Turn OFF gas supply 4 Wait five minutes...

Страница 5: ...crease the SET water temperature in single increments Refer to OPERATING INSTRUCTIONS WITH OPTIONAL ON DEMAND CONTROL CENTER and see Figure 13 LOW TEMPERATURE RISE AND EXCESSIVE WATER FLOW REQUIRED TO...

Страница 6: ...pply to heater 3 Shut off water supply Drain water from system 4 Disconnect HOT and COLD water lines from water heater 5 Remove screws at the back of the unit 6 Remove vent cap assembly 7 Remove water...

Страница 7: ...1 2 I D TUBING Figure 5 VENT CAP PART NO 260617 SHOWN FOR INSTALLATION WITHOUT ACCESS PANEL MAX X DIMENSION OF 2 00 1 250 MIN OVERLAP REQUIRED ON EXHAUST X ON DEMAND WATER HEATER EXHAUST VENT TUBE TRA...

Страница 8: ...AROUND OPENING 8 SCREWS 4 SCREWS MOUNTING TABS IN FRAME 2 SLOTS IN BOTTOM OF PANEL HOOK IN TABS ON FRAME BEFORE INSTALLING 5 SCREWS TO SECURE PANEL BOTTOM OF PANEL SILICONE OR CAULKING AROUNG OPENING...

Страница 9: ...AIN 5 8 I D TUBING SYSTEM DRAIN CONTROL KNOB FREEZE PROTECTION NEEDLE VALVE CONDENSATE DRAIN 1 2 I D TUBING GREEN GROUND SCREW Figure 10 Figure 9 SERVICE PANEL MANUAL ECO SWITCH LEFT SIDE ACCESS PANEL...

Страница 10: ...MPERATURE PROBE OUTLET WATER TEMPERATURE PROBE WH WH BR BR Y R GAS VALVE 2 STAGE GAS VALVE R SPARK ELECTRODE ON DEMAND CONTROL CENTER MOTOR WH O BR Y GY R BL WIRE HARNESS SWITCH R LAMP BK MODULE BOARD...

Страница 11: ...reached the display stops flashing after a few seconds B When the demand for hot water has been terminated the display will return to the SET Temperature C When the water heater is turned off the lett...

Страница 12: ...IONS MAY NOT APPLY TO YOU THE EXPRESSED WARRANTIES MADE IN THIS WARRANTY ARE EXCLUSIVE AND MAY NOT BE ALTERED ENLARGED OR CHANGED BY ANY DISTRIBUTOR DEALER OR OTHER PERSON WHOMSOEVER SUBURBAN WILL NOT...

Страница 13: ...ENTE GARANTIE SONT EXCLUSIVES ET NE PEUVENT PAS TRE MODIFI ES TENDUES OU CHANG ES PAR UN DISTRIBUTEUR UN CONCESSIONNAIRE OU UNE AUTRE PERSONNE QUELLE QU ELLE SOIT SUBURBAN NE SERA PAS TENUE RESPONSABL...

Страница 14: ...hage cesse de clignoter au bout de quelques secondes B Lorsque la demande en eau chaude prend fin l affichage retourne la temp rature de consigne C Lorsque le chauffe eau est teint les lettres OF s af...

Страница 15: ...OURNI AVEC L APPAREIL DOIT ETRE REMPLACE LE REMPLACER PAR UN MATERIAU DE CABLAGE AYANT UNE TEMPERATURE MINIMALE D AU MOINS 80 C 176 F CAL 20 600 V 105 C 221 F CAL 18 600 V 105 C 221 F MISE EN GARDE N...

Страница 16: ...BOUTON DE COMMANDE DE LA VIDANGE DU CIRCUIT AIGUILLE DE SOUPAPE FREEZE PROTECTION VIDANGE DU CONDENSATS 1 2 PO DIMENSIONS INTERNES TUBE VERT SOL VIS Figure 10 Figure 9 PANNEAU D ENTRETIEN INTERRUPTEUR...

Страница 17: ...OU CALFEUTRE AUTOUR DE L OUVERTURE POUR LE PANNEAU D ACCES 37 8 LITERS 10 GALLONS LE CAS ECHEANT 4 VIS 5 VIS APPLIQUER DU SILICONE AUTOUR DU COTE ARRIERE DU TROU D AERATION DIOT ETRE SCELLE AU PANNEA...

Страница 18: ...DU CONDENSATS 1 2 PO DIMENSIONS INTERNES TUBE Figure 5 PI CE POUR BOUCHON D VENT NO 260617 MONTR E POUR L INSTALLATION SANS PANNEAU D ACC S DIMENSIONS MAX X DE 5 08 cm X ON DEMAND WATER HEATER CLAPET...

Страница 19: ...HEATER 1 Fermer l alimentation en gaz et d brancher le tuyau d alimentation en gaz du chauffe eau 2 D brancher l alimentation 12 Vcc du chauffe eau 3 Fermer l alimentation en eau vacuer l eau du syst...

Страница 20: ...Si votre chauffe eau n cessite un d bit excessif pour tre activ plus de 1 9 LPM il est possible que de l eau FROIDE soit purg e dans le c t de l eau CHAUDE de votre syst me de distribution d eau 1 V r...

Страница 21: ...br leur ne s allume pas le syst me tentera automatiquement d effectuer deux autres essais d allumage avant le verrouillage Lorsque la lumi re demeure allum e le syst me est en mode verrouillage 8 Si...

Страница 22: ...URBAN 22 7 LITRES 6276APW Blanc polaire SUBURBAN 37 8 45 42 60 5 LITRES 6277APW Blanc polaire ATWOOD 22 7 LITRES 521147 Blanc polaire ATWOOD 37 85 LITRES 521150 Blanc polaire NUM RO DE PI CE DU BOUCHO...

Страница 23: ...e l unit est recommand e pour att nuer l accumulation de charge lectrostatique en fixant un fil isol de mise de terre de calibre 12 au bo tier de l unit la vis de terre verte illustr e la Figure 5 et...

Страница 24: ...APPOSER CES INSTRUCTIONS SUR OU PROXIMIT DU CHAUFFE EAU PROPRI TAIRE CONSERVER CES INSTRUCTIONS ET LA GARANTIE AUX FINS DE CONSULTATION ULT RIEURE TOUTES QUESTIONS DE NATURE TECHNIQUE OU RELATIVES LA...

Отзывы: