11
12
OL
Parameter
17
Function : To set Over current limit.
To change the OL parameter,
press the set key.
Use UP/DOWN keys to set desired
value.
This parameter used to switch off the
compressor incase it draws higher
current than the set current.
Example :
If this parameter is set at
10.0A, the controller will trip compressor
if it draws more than 10.0A.Controller
will restart the compressor after the set
time delay. If after 3 retries within 1hour,
current drawn is still more than 10.0A,
the controller will trip the compressor on
fault and activate the respective alarm
relay. Also display will flash “OL”.
(UL+1.0)A
18.0A
10.0A
Range
Min
Max
Fact. Set
Range
Min
Max
Fact. Set
If this parameter is set to
ENB = HP sensing is enabled.
Example :
Use UP/DOWN keys to set desired value.
DIS = HP sensing is disabled
Setting this parameter to disable will
ignore HP fault for compressor. If this
parameter is set to Enable then controller
will detect HP trip.
To change the D0 parameter,
press the set key.
D0
Parameter
19
Function : To enable or Disable HP
sensing.
DIS
ENB
ENB
Range
Min
Max
Fact. Set
To change the C2 parameter,
press the set key.
C2
Parameter
18
Function: To set Current sensing delay.
Use UP/DOWN keys to set desired
value.
Example :
If C2 parameter is 1 Sec
then, any current fault will be valid only
when it exsists for more than 1 sec.
5 Sec
60 Sec
5 Sec
Range
Min
Max
Fact. Set
Range
Min
Max
Fact. Set
Sr.
No.
Parameter setting method
Description of parameters and functions.
Parameter
Sr.
No.
Parameter setting method
Description of parameters and functions.
Parameter
Parameter
D2
21
press the set key.
To change D2 parameter,
0V
230V
Function: To set fault sensing logic.
230V
0v = 0V at HP/LP/AUX input will be
sensed as fault and trip the
compressor.
Use UP/DOWN keys to set desired
value.
230V = 230V at HP/LP/AUX input will be
compressor.
sensed as fault and trip the
Range
Min
Max
Fact. Set
Example :
If this parameter is set at
1.0A, the controller will trip compressor if
it draws less than 1.0A. Controller will
restart the compressor after the set time
delay. If after 3 retries within 1hour,
current drawn is still less than 1.0A, the
controller will trip the compressor on fault
and activate the respective alarm relay.
Also display will flash “UL”.
DIS = LP sensing is disabled.
Example:
Use UP/DOWN keys to set desired
value.
ENB = LP sensing is enabled.
If this parameter is set to
Setting this parameter to disable will
ignore LP fault for compressor. If this
parameter is set to Enable then controller
will detect LP trip.
parameter, press the set key.
To change D1
DIS
ENB
D1
Parameter
20
ENB
Function: To enable or disable LP
sensing.
Range
Min
Max
Fact. Set