11

12

OL
Parameter

17

Function : To set Over current limit.

To change the OL parameter, 
press the set key.

Use UP/DOWN keys to set desired 
value.

This parameter used to switch off the 
compressor incase it draws higher 
current than the set current. 

Example :

 If this parameter is set at 

10.0A, the controller will trip compressor 
if it draws more than 10.0A.Controller 
will restart the compressor after the set
time delay. If after 3 retries within 1hour, 
current drawn is still more than 10.0A, 
the controller will trip the compressor on 
fault and activate the respective alarm 
relay. Also display will flash “OL”.

(UL+1.0)A

18.0A

10.0A

Range

Min 

Max 

   Fact. Set 

Range

Min 

Max 

   Fact. Set 

If this parameter is set to

ENB = HP sensing is enabled.

Example : 

Use UP/DOWN keys to set desired value.

DIS   = HP sensing is disabled

Setting this parameter to disable will 
ignore HP fault for compressor. If this 
parameter is set to Enable then controller 
will detect HP trip. 

To change the D0 parameter, 
press the set key.

D0
Parameter

19

Function  :  To  enable  or  Disable  HP 
sensing. 

DIS 

ENB

ENB

Range

Min 

Max 

   Fact. Set 

To change the C2 parameter, 
press the set key.

C2
Parameter

18

Function: To set Current sensing delay.

Use UP/DOWN keys to set desired 
value.

Example : 

If C2 parameter is 1 Sec 

then, any current fault will be valid only 
when it exsists for more than 1 sec.

5 Sec

60 Sec

5 Sec

Range

Min 

Max 

   Fact. Set 

Range

Min 

Max 

   Fact. Set 

Sr. 

No. 

Parameter setting method

Description of parameters and functions.

Parameter 

Sr. 

No. 

Parameter setting method

Description of parameters and functions.

Parameter 

Parameter

D2

21

press the set key.

To change D2 parameter, 

0V

230V

Function: To set fault sensing logic.

230V

0v =  0V at HP/LP/AUX input will be 
 

sensed as fault and trip the 

 

    compressor.

Use UP/DOWN keys to set desired 
value.

230V =  230V at HP/LP/AUX input will be 

 

compressor.

 

    sensed as fault and trip the 

          

Range

Min 

Max 

   Fact. Set 

Example : 

If this parameter is set at 

1.0A, the controller will trip compressor if 
it draws less than 1.0A. Controller will 
restart the compressor after the set time 
delay. If after 3 retries within 1hour, 
current drawn is still less than 1.0A, the 
controller will trip the compressor on fault 
and activate the respective alarm relay. 
Also display will flash “UL”.

DIS   = LP sensing is disabled.

Example:  

Use UP/DOWN keys to set desired 
value.

ENB = LP sensing is enabled.

If this parameter is set to 

Setting this parameter to disable will 
ignore LP fault for compressor. If this 
parameter is set to Enable then controller 
will detect LP trip. 

parameter, press the set key.

To change D1

DIS 

ENB

D1 
Parameter

20

ENB

Function: To enable or disable LP 
sensing.

Range

Min 

Max 

   Fact. Set 

Содержание CRC-1023

Страница 1: ...COLD ROOM CONTROLLER USER MANUAL www pvrcontrols com INDIA CRC 1023...

Страница 2: ...To set time delay for voltage sensing V1 10 To set Over current limit OL 11 To set Under current limit UL 10 11 Key Introduction 5 To set Current sensing delay C2 11 D0 To enable or Disable HP sensing...

Страница 3: ...ch the defrost is interrupted There are safety features which include shutting down the system incase of a fault from a pressure control or similar device The CRC 1023 are single set point cold room c...

Страница 4: ...till the AL delay is over controller will not generate HTAlarm Example Setting this parameter Use UP DOWN key to set desired value Once set at a particular value this will not allow the set point to g...

Страница 5: ...al is 2 0 C the 0 comp Relay will cutin at 12 0 C Use UP DOWN keys to set desired value 0 0 10 0 C 2 0 C 04 P4 Parameter Function To set the differential for compressor restart To change P4 parameter...

Страница 6: ...t will show OV fault on display and Compressor Relay will be off Parameter V1 15 Function To set time delay for voltage sensing To change the V1 Parameter parameter press the set key Use UP DOWN keys...

Страница 7: ...xample If C2 parameter is 1 Sec then any current fault will be valid only when it exsists for more than 1 sec 5 Sec 60 Sec 5 Sec Range Min Max Fact Set Range Min Max Fact Set Sr No Parameter setting m...

Страница 8: ...palyed Use UP DOWN keys to set desired value TEMP At defrosting temperature 27 Function To set Display at defrosting To change E7 parameter press the SET key TEMP DEF TEMP Range Min Max Fact Set Range...

Страница 9: ...er into program mode only if correct password is entered If the password is wrong it will show INVALID PASSWORD Range Min Max Fact Set Range Min Max Fact Set NO YES NO To change FS parameter press the...

Страница 10: ...0Vac Defrost 20A 250Vac Evap Relay 10 3 A 250Vac 0 0 Operating Temp 5 C to 50 C non condensing 0 0 Storage temp 20 C to 70 C non condensing Output Input 1 NTC Probe 0 0 Range 50 0 C to 50 0 C 0 Resolu...

Страница 11: ...d personnel only Controller Controller should be installed in a place protected by vibration water and corrosive gasses and where ambient temperature does not exceed the values specified in the techni...

Страница 12: ...taken in the preparations of this document the company or its vendors in no event will be liable for direct indirect special incidental or consequential damage arising out of the use or inability to...

Отзывы: