Key Introduction

Auxiliary/Fault Log Key 

Alarm Reset Key

Defrost Key

RST

AUX

PRG

Program Key 

Up/Volt Key 

SET

Down/Amp. Key

Set Key

Power Key

Lamp ON/OFF Key

Press PRG Key to Enter Programming mode 

/ ESC Key

1> USER PROGRAM

                  MAIN SYSTEM PROGRAMMING MODE

Press AUX/FAULT LOG Key to View last 
9 Fault Log.

3> FAULT LOG

05

SET POINT

To set the cut-out point of the controller.

Display will change to set value.
The set point value can now be changed 
by using the UP/DOWN key. After 
desired value, press the SET key & you 
will see “--” which confirms that the set 
point has been stored in memory. 

01

Press and hold SET key 
for 2 seconds and 
Release.

P3+0.5

P2-0.5

0.0ºC

SET

Min : MINIMUM   Max : MAXIMUM
Fact. Set : FACTORY SETTING(DEFAULT)

Sr. 

No. 

Parameter setting method

Description of parameters and functions.

Parameter 

Range

Min 

Max 

   Fact. Set 

02

P2 
Parameter

Function : To set maximum allowable 
high temperature limit. 

To change P2 parameter, 
press the set key.

0

at 30.0 C  will not allow  the set point to go 

0

above  30.0 C  also  if  the    temperature 

0

reaches 30.0 C, the display will show  HT 
(High  Temperature).  The  alarm  will  be 
ON.  But  at  power  on  till  the AL  delay  is 
over controller will not generate HT Alarm. 

Example : 

Setting this parameter

Use UP/DOWN key to set desired value. 
Once set at a particular value, this will 
not allow the set point to go above this
value and below P3 setting.

03

Parameter

P3

Function : To set minimum allowable low 
temperature limit.

Use UP/DOWN key to set desired value. 
Once set at a particular value, this will 
not allow the set point to go below this 
value and above P2 setting.

Example 

 

Setting this parameter

0

at -30.0 C will not allow  the set point to 

0

go below -30.0 C also if the temperature 

0

reaches -30.0 C, the display will show  
LT (Low Temperature). The alarm will be 
ON. 

To change P3 parameter, 
press the set key.

SP+0.5

50.0ºC

50.0ºC

-50.0ºC

Set Point

-0.5ºC

-50.0ºC

06

PRG

To set other parameter

Press & hold PRG key for 
2 seconds 

Display will show ‘P2’ and scroll the 
description of the parameter.
To go to other parameters ,
use up / down keys.

Range

Min 

Max 

   Fact. Set 

Sr. 

No. 

Parameter setting method

Description of parameters and functions.

Parameter 

Range

Min 

Max 

   Fact. Set 

Press RST Key to reset alarm relay & buzzer.

4> Mute

Press SET Key to Enter Set mode.

2> SET MODE

Press Defrost  Key for manual defrost.

5> Manual Defrost

Press Down/Amp Key to see the compressor 
current.

6> View Current

Press UP/Volt Key to see the voltage.

7> View Voltage

Содержание CRC-1023

Страница 1: ...COLD ROOM CONTROLLER USER MANUAL www pvrcontrols com INDIA CRC 1023...

Страница 2: ...To set time delay for voltage sensing V1 10 To set Over current limit OL 11 To set Under current limit UL 10 11 Key Introduction 5 To set Current sensing delay C2 11 D0 To enable or Disable HP sensing...

Страница 3: ...ch the defrost is interrupted There are safety features which include shutting down the system incase of a fault from a pressure control or similar device The CRC 1023 are single set point cold room c...

Страница 4: ...till the AL delay is over controller will not generate HTAlarm Example Setting this parameter Use UP DOWN key to set desired value Once set at a particular value this will not allow the set point to g...

Страница 5: ...al is 2 0 C the 0 comp Relay will cutin at 12 0 C Use UP DOWN keys to set desired value 0 0 10 0 C 2 0 C 04 P4 Parameter Function To set the differential for compressor restart To change P4 parameter...

Страница 6: ...t will show OV fault on display and Compressor Relay will be off Parameter V1 15 Function To set time delay for voltage sensing To change the V1 Parameter parameter press the set key Use UP DOWN keys...

Страница 7: ...xample If C2 parameter is 1 Sec then any current fault will be valid only when it exsists for more than 1 sec 5 Sec 60 Sec 5 Sec Range Min Max Fact Set Range Min Max Fact Set Sr No Parameter setting m...

Страница 8: ...palyed Use UP DOWN keys to set desired value TEMP At defrosting temperature 27 Function To set Display at defrosting To change E7 parameter press the SET key TEMP DEF TEMP Range Min Max Fact Set Range...

Страница 9: ...er into program mode only if correct password is entered If the password is wrong it will show INVALID PASSWORD Range Min Max Fact Set Range Min Max Fact Set NO YES NO To change FS parameter press the...

Страница 10: ...0Vac Defrost 20A 250Vac Evap Relay 10 3 A 250Vac 0 0 Operating Temp 5 C to 50 C non condensing 0 0 Storage temp 20 C to 70 C non condensing Output Input 1 NTC Probe 0 0 Range 50 0 C to 50 0 C 0 Resolu...

Страница 11: ...d personnel only Controller Controller should be installed in a place protected by vibration water and corrosive gasses and where ambient temperature does not exceed the values specified in the techni...

Страница 12: ...taken in the preparations of this document the company or its vendors in no event will be liable for direct indirect special incidental or consequential damage arising out of the use or inability to...

Отзывы: