No. 

Parameter setting method

Description of parameters and functions.

Parameter 

ENB : Buzzer Enabled.
DIS : Buzzer Disabled.
     

Use UP/DOWN keys to set desired value.

10

BUZ
Parameter

Function: To enable or disable Buzzer.

To change 

BUZ 

parameter, 

press the set key.

DIS

ENB

ENB

Range

Min 

Max 

   Fact. Set 

Use the UP/DOWN keys to get desired 
value and press SET key. 

11

Parameter

AL

Function: Power on time delay for alarm.

To change 

AL 

parameter, 

press the set key.

0 Min

99 Min

30 Min

Range

Min 

Max 

   Fact. Set 

Example : 

If this parameter is set to 

180V then if the voltage is less than 
180V it will show UV fault on display and 
Compressor Relay will be off.

Use UP/DOWN  keys to set desired 
value. 

12

UV
Parameter

Function: To set under voltage limit.

press the set key.

To change 

UV 

parameter, 

180V

(OV-10)V

180V

Range

Min 

Max 

   Fact. Set 

Sr. 

No. 

Parameter setting method

Description of parameters and functions.

Parameter 

OV
Parameter

13

Function : To  set over voltage limit

To change the OV Parameter 
parameter, press the set key.

Use UP/DOWN keys to set desired value. 

(UV+5)V

260

240

Range

Min 

Max 

   Fact. Set 

Example :  

If this parameter is set to 

240V then if the voltage is above than 
240V  it will show OV fault on display 
and Compressor Relay will be off.

Parameter

V1

15

Function : To set time delay for 
voltage sensing.

To change the V1 Parameter 
parameter, press the set key.

Use UP/DOWN keys to set desired value. 

5 Sec

30 Sec

5 Sec

Range

Min 

Max 

   Fact. Set 

Example :  

If V1 parameter is 5, then if 

voltage  fault condition occures and 
stays continuously for 5 sec then only 
fault is valid. 

UL
Parameter

16

Function : To set Under current limit.

To change the UL Parameter 
parameter, press the set key.

Use UP/DOWN keys to set desired value. 

0.0A

(OL-1.0)A

1.0A

Range

Min 

Max 

   Fact. Set 

This parameter used to switch off the 
compressor incase it draws lower 
current than the set current. 

V0
Parameter

14

Function : To set voltage differential.

To change the V0 Parameter 
parameter, press the set key.

Use UP/DOWN keys to set desired value. 

5V

50V

5V

Range

Min 

Max 

   Fact. Set 

Example : 

 If this parameter is set to 5V 

then for OV fault when voltage is grater 
than OV-5 then only this fault is cleared. 
For UV fault then when the voltage is 
greater than UV+5 then only UV fault 
will be cleared.

09

10

Example : 

If you set this parameter to 

20min, once the power is switch on, the 
alarm for Ht/Lt will not activate for 20 
minutes after the power is switched on. 
This is most useful to avoid the nuisance 
alarms when the ambient are high when 
machine is switched on after long time.

Содержание CRC-1023

Страница 1: ...COLD ROOM CONTROLLER USER MANUAL www pvrcontrols com INDIA CRC 1023...

Страница 2: ...To set time delay for voltage sensing V1 10 To set Over current limit OL 11 To set Under current limit UL 10 11 Key Introduction 5 To set Current sensing delay C2 11 D0 To enable or Disable HP sensing...

Страница 3: ...ch the defrost is interrupted There are safety features which include shutting down the system incase of a fault from a pressure control or similar device The CRC 1023 are single set point cold room c...

Страница 4: ...till the AL delay is over controller will not generate HTAlarm Example Setting this parameter Use UP DOWN key to set desired value Once set at a particular value this will not allow the set point to g...

Страница 5: ...al is 2 0 C the 0 comp Relay will cutin at 12 0 C Use UP DOWN keys to set desired value 0 0 10 0 C 2 0 C 04 P4 Parameter Function To set the differential for compressor restart To change P4 parameter...

Страница 6: ...t will show OV fault on display and Compressor Relay will be off Parameter V1 15 Function To set time delay for voltage sensing To change the V1 Parameter parameter press the set key Use UP DOWN keys...

Страница 7: ...xample If C2 parameter is 1 Sec then any current fault will be valid only when it exsists for more than 1 sec 5 Sec 60 Sec 5 Sec Range Min Max Fact Set Range Min Max Fact Set Sr No Parameter setting m...

Страница 8: ...palyed Use UP DOWN keys to set desired value TEMP At defrosting temperature 27 Function To set Display at defrosting To change E7 parameter press the SET key TEMP DEF TEMP Range Min Max Fact Set Range...

Страница 9: ...er into program mode only if correct password is entered If the password is wrong it will show INVALID PASSWORD Range Min Max Fact Set Range Min Max Fact Set NO YES NO To change FS parameter press the...

Страница 10: ...0Vac Defrost 20A 250Vac Evap Relay 10 3 A 250Vac 0 0 Operating Temp 5 C to 50 C non condensing 0 0 Storage temp 20 C to 70 C non condensing Output Input 1 NTC Probe 0 0 Range 50 0 C to 50 0 C 0 Resolu...

Страница 11: ...d personnel only Controller Controller should be installed in a place protected by vibration water and corrosive gasses and where ambient temperature does not exceed the values specified in the techni...

Страница 12: ...taken in the preparations of this document the company or its vendors in no event will be liable for direct indirect special incidental or consequential damage arising out of the use or inability to...

Отзывы: