Electronic Control System
Integrated
(700-
3
BASE)
Series
3-20
#3758424 - Revision B - December, 2005
UNIT
ICE
REFRIGERATOR
ON/OFF
ON/OFF
ON/OFF
WARMER
COLDER
FREEZER
WARMER
COLDER
OFF
SERVICE
ICE
UNIT
ICE
REFRIGERATOR
ON/OFF
ON/OFF
ON/OFF
WARMER
COLDER
FREEZER
WARMER
COLDER
OFF
SERVICE
ICE
Figure 3-36. “EE” Observed in Diagnostic Mode = Thermistor Fault in Location Indicated by Code
Figure 3-37. “Sr” Observed While in Diagnostic Mode = Unit is in Showroom Mode
If “Sr” is observed at left display area during Diagnostic Mode, the unit is in Showroom Mode, which was explained
earlier in this section (See Figure 3-37).
If “EC” is observed in the right display area during Diagnostic Mode, the numbers at left are “Error Codes” (See
Figure 3-38). Error Codes indicate problems registered by specific components. If error codes are registered, they
will appear before temperature readings and can be toggled through with the temperature readings as described on
the previous page. (See Error Code Table below and instructions on clearing Error Codes on next page.)
UNIT
ICE
REFRIGERATOR
ON/OFF
ON/OFF
ON/OFF
WARMER
COLDER
FREEZER
WARMER
COLDER
OFF
SERVICE
ICE
Figure 3-38. “EC” Observed While in Diagnostic Mode = Error Code
(See table below & how to clear Error Codes on next Page)
700BCI-3 Error Code Table
CODE INDICATION
05
Refrig. cabinet thermistor read open or shorted for 10+ seconds, or repeatedly read erratic temp’s
07
Freezer cabinet thermistor read open or shorted for 10+ seconds, or repeatedly read erratic temp’s
08
Freezer evaporator thermistor read open or shorted for 10+ seconds, or repeatedly read erratic temp’s
20
Defrost under-heat with no voltage feedback through Gray/White wire at defrost start
21
Defrost overheat
22
No voltage feedback through Gray/White wire at defrost start
23
Defrost overheat with no voltage feedback through Gray/White wire at defrost start
24
Defrost under-heat
30
Excessive Icemaker Water Valve Solenoid Activation (Exceeded 15 Seconds)
40
Excessive Freezer Compressor Run
50
Excessive Refrigerator Fan Run
Diagnostic Mode Indicators
If “EE” is observed in left display area during Diagnostic Mode, the thermistor in that location is open or shorted, or
there is a break in that thermistor’s wiring (See Figure 3-36).
Содержание 700-3 BASE
Страница 2: ......
Страница 12: ...Installation Information Integrated 700 3 BASE Series 2 4 3758424 Revision B December 2005 ...
Страница 40: ...Electronic Control System Integrated 700 3 BASE Series 3 28 3758424 Revision B December 2005 ...
Страница 48: ...Sealed System Information Integrated 700 3 BASE Series 4 8 3758424 Revision B December 2005 ...
Страница 52: ...Airflow Fan Blade Spacing Integrated 700 3 BASE Series 5 4 3758424 Revision B December 2005 ...
Страница 58: ...Icemaker Information Integrated 700 3 BASE Series 6 6 3758424 Revision B December 2005 ...
Страница 101: ...Technical Data Integrated 700 3 BASE Series 9 1 3758424 Revision B December 2005 SECTION 9 TECHNICAL DATA ...
Страница 114: ...Wire Diagrams Schematics Integrated 700 3 BASE Series 10 10 3758424 Revision B December 2005 ...