22
EN/05.2019 © STULZ GmbH – all rights reserved
CYBERHANDLER 2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Climatizadores · Condensadores · Aero-refrigeradores · Fan Coils ·Baterias
Air Handlers · Condensers · Dry-Coolers · Air-heaters · Coils
6.4.2. Adiabatic system
N
ew sketch to insert in the IOM manual (replacing the current sketch, p.21)
:
Fig 6-9: water connection
Cooling Coil:
Water draining (O 1.’’ GAS)
Adiabatic system:
water connection of
upper module
Adiabatic system:
Water draining
(Ø 1
1/2
" GAS)
Adiabatic system:
Water filling
(Ø 3/4" GAS)
10
Water cuality
Circulation water max
Material in contact with water
•
Stainless steel
•
Aluminum
•
Epoxy coating
•
Plastics
Appearance
-
Clear, colourless, without
sediment
pH value
-
7.5 to 8.5
Total salt content
g/m
3
<1400
Electrical conductivity (25 ºC)
µS/cm
<1600
Hardness
KH
ºdH
<1
Chloride
CL-
g/m
3
<100
Sulphate
SO42-
g/m
3
<280
Cu-ionen
CU2+
g/m
3
< 0,05
KMnO4
g/m
3
< 50