72
EN/09.2019/G41 © STULZ GmbH – all rights reserved
cybercool 2 screw original insTrUcTions
Electrical cabinet control section, right side
User interface
with display
Driver module for electro-
nic expansion valve plus
battery module
IO controller board
Service-Port X15
for connection of a PC/lap-
top for operation
Release switch for compressor
protection device, circuit 1
Release switch for compressor
protection device, circuit 2
NOtICE
Damage to the compressor by liquid refrigerant
If the unit is switched off via the main switch without first switching off the control (start/stop
button or „state stop“ command), the expansion valve is closed using the battery. When the bat-
tery is discharged, the valve in this case retains its current opening degree. The open expansion
valve allows liquid refrigerant to flow into the evaporator.