23
Gerätetyp
ESO/EQO ... ASN/ASF
12 °C
ESO/EQO ... AHN/AHF
20 °C
© STULZ GmbH – all rights reserved EN/09.2019/G41
cybercool 2 screw original insTrUcTions
Storage conditions:
Temperature [°C]:
-20 - +45
Humidity [% rel. h.]:
5 - 95
type of network:
TN-S; TN-C-S
Voltage:
400V/50Hz/3Ph/N/PE
Voltage tolerancy:
+/- 10 % (not for permanent operation)
Frequency tolerancy:
+/- 1 %
Rated ultimate short-circuit breaking capacity
(I
Cu
):
25 kA
Required minimum thermal load:
20% of nominal cooling capacity
Chilled water conditions:
Max. temperature at the unit inlet:
+26 °C
Temperature difference:
4–8 K
Max. water pressure:
10 bar
Max. glycol content:
35%
with special pumps:
to 50%
Max. temperature at the unit outlet:
Requirements for electric network and uPS
systems:
• the output voltage of the electric network or UPS
system must be grounded neutral (wye).
• the voltage distortions must be within the limits
stated below and no inadmissibly high DC voltage
portions may exist.
transient peak over-voltage phase to ground:
max. 4 kV (1,2/50µs wave form; Z=12 Ohms in acc.
to ANSI)
transient peak over-voltage phase to phase:
max. 2 kV (1,2/50µs wave form; Z=2 Ohms in acc.
to ANSI)
ripple voltage phase to ground:
dV/dt < 1V/µs (
≡
1000V/ms)
voltage harmonics: THD(V) < 8%
• all-pole sinus filters must be provided at the UPS
system output.
The warranty is invalidated for any possible damage
or malfunction that may occur during or in conse-
quence of operation outside the application limits.
4. technical Data
4.1 Application limits
at maximum compressor capacity, water volume flow
according to design conditions 18/12°C and outdoor
temperature 35°C. The temperatures may vary during
the start phase.
Chiller type
• Set the water temperature setpoint consequently.
Содержание CyberCool 2
Страница 4: ...4 4 EN 09 2019 G41 STULZ GmbH all rights reserved CYBERCOOL 2 SCREW ORIGINAL INSTRUCTIONS...
Страница 101: ......