The electrical reheat is an optional extra for the A/C unit. It is completely installed and integrated in the function and
method of operation of the A/C unit. It is used to heat up the air. The following versions of the electrical reheat which
is single-stage are available:
- 3 x 0,7 kW for construction size 1
- 3 x 2,0 kW for construction size 2
The reheat is connected in accordance with the
electric diagram. It is controlled and monitored by
the controller. The values for switching on and off
are adjusted in the "operate/components/heating"
menu on the controller. Refer to the operating in-
structions C7000.
Maintenance
Clean the reheat annually from contaminations and
check it for damage.
12.5 Electrical reheat
electrical
reheat
elements
Malfunction causes
Alarm: E-HEAT 1 FAILURE (display by C7000 controller)
Cause
:
The temperature switch at the reheat element or the reheat power switch has triggered.
Effect
:
The electrical reheat is switched off by the C7000 controller.
Example: CRS 320 CW