8. Maintenance
8.1 Safety instructions
All maintenance work is to be carried out under strict compliance with the country-specific accident prevention regu-
lations. In particular we refer to the accident prevention regulations for electrical installations, refrigerating machines
and equipment. Non-compliance with the safety instructions can endanger people and the environment.
Maintenance work is only to be carried out on the units by authorized and qualified specialist staff.
Procedure instructions
Work on the system must always only be carried out when it is shut down. To do this, the unit must be
switched off at the controller and at the master switch. A „DO NOT SWITCH ON“ warning sign must be
displayed.
Live electrical components are to be switched to de-energized and checked to ensure that they are in the
de-energized state.
Some verifications must be effected with the unit in operation (measuring the current, pressures, temperatu-
res). In such a case the unit must only be switched on at the master switch after all mechanical connections
have been established. The unit must be switched off immediately after the measuring procedure.
Warning notes!
When the master switch is switched on and the controller is stopped the power contactors are live,
even if the components are not operating.
At the fan contactor, dangerous voltages occur. Do not open the unit within the first 5 minutes after
disconnection of all phases. Be sure that the unit is being isolated.
In units with 2 or 3 fans dangerous charges of >50µC can occur between AC line terminals and PE
after disconnection.
The electronics housing can get hot.
The fans have an operation delay after the unit is stopped ! (Risk of injury
)
8.2 Maintenance intervals
Component
Maintenance interval
quarterly
half-yearly
yearly
Refrigerant circuit
Refrigerant charge
HP switch
Sight glass
Compressor
Expansion valve
x
x
x
x
x
Air circuit
Heat exchanger
Fan
Air filter
x
x
x
Water circuit
Tightness
Condenser
x
x
Unit in general
Electrics
Mechanics
x
x