31
/04.2016/
G35
Baugröße
A
B
S
1,8 m
2,4 m
1
2,4 m
2,4 m
2
3,0 m
3,6 m
CyberRo
w
CyberRo
w
CyberRo
w
EN
Due to the lateral position of air discharge openings, CyberRow units must be installed protruding in the cold aisle
from the front of the rack line: 120 mm for sizes S and 1 / 160 mm for size 2.
Min. clearance:
120 mm for size S and 1
160 mm for size 2
When CyberRow works at reduced capacity, also the supply air speed decreases, therefore the most
distant racks from the CyberRow unit are provided with less cold air. These should be the racks
with the minimum heat load.
To control temperature at the intake of most distant rack from the unit, remote probes to measure
supply air temperature are available as accessory.
There are no limits for the maximum width of aisles, because cold air is not dispersed in the entire cold aisle, but is
supplied in a thin layer near the surface of the racks. Minimum width of aisles is determined by the space necessary
for maintenance in the front and rear sides of the unit, as well as by applicable safety standards.
The number of racks served by one CyberRow unit, as well as the distribution of the units in the rows, must be de-
cided from time to time according to the heat load per rack and the desired redundancy in case of failure. Contact
STULZ for any assistance regarding the design of the site.
Distance A/C – end of a row:
min 0.6 m ÷ max A
Distance between A/Cs:
min 1.8 m ÷ max B
Top view
Size