CPU- Address can be entered in this item. If CompTrol 1002 is connected to a STULZ
Monitoring System, an address between 1 and 32 for every connected controller has
to be adjusted.
Temperature Sensor Adjustment
Temperature sensor adjustment can be done in this item. The actual value is indica-
ted and can be adjusted to another value, that is measured by use of an independent
temperature sensor.
Display is in reference to position of DIP- switch 4 degrees Celsius
or Fahrenheit.
By loading the basic program of the controller, sensor adjustment
is reset to zero.
Humidity Sensor Adjustment
Humidity sensor adjustment can be done in this item. The actual value taken from a
reference measurement has to be entered.
By loading the basic program of the controller, sensor adjustment
is reset to zero.
Unit Start Delay
Unit start delay can be entered in this item. This is the time, the unit start is delayed in
addition to the initialization time, when the unit is turned on in start mode (Autostart)
The start delay can be entered in 4-second intervals.