2. Setpoint temperature
3. Setpoint humidity
4. Limit value temperature too high
5. Limit value temperature too low
6. Limit value humidity too high
7. Limit value humidity too low
8a. Valve modulating time
8b. Compressor restart delay
9a. CW-valve start value
9b. Compressor 1 start value
10a. CW valve proportional range
10b. Hysteresis compressors
11a. Opening degree for dehumidif.
11b. Compressor 2 start value
12. Start value reheat 1
13. Hysteresis reheat 1 + 2
14. Start value reheat 2
15. Start value humidification
16. Hysteresis humidification
17. Start value dehumidification
18. Hysteresis dehumidification
19. CPU-address
20. Sensor adjustment "temperature"
21. Sensor adjustment "humidity"
22. Unit start delay
23. Integral factor
24. Sequencing for 2 units
Menu item
Range
Standard
value
Adjusted value
9. Appendix
9.1 Standard Setting