background image

(© Oct, 2007)

Air Technology Systems, Inc.

Compact CW Series Installation, Operation & Maintenance Manual

2-9

2.8.2

Controls

SATS offers a wide range of control features to solve
your air conditioning control/alarm requirements. The
Compact CW system is furnished with a C1002 or
C6000 Microprocessor controller. If it is mounted on
the unit (standard), no utility connection is required. As
an option a factory supplied display may be remote
mounted. A six-conductor cable harness is provided for
interconnect wiring. Refer to the electrical drawing
provided with the unit for details on interconnecting
field wiring.

2.8.3

Optional Equipment

Additional control conductors may be required depend-
ing on the options purchased with the equipment.
Refer to the electrical diagram supplied with your unit
to determine the total number of interconnecting
conductors required for your system. It is important to
note that control transformer(s) supplied with the
equipment are sized and selected based upon the
expected loads for each system.

CAUTION

 

Do not connect any additional loads to the sys-
tem control transformers. Connecting additional
loads to the factory supplied control transformer
may result in overloading of the transformer.

NOTE

All wiring must be provided in accordance with
local and national electrical code requirements.

2.7.3.1 Remote Temperature/Humidity Sensor

The remote temperature/humidity sensor requires a
three conductor shielded cable, with the shield
terminated at the unit electric box. Both the electric
box and the sensor are provided with a terminal strip
for the wire connections. Refer to the electrical
schematic supplied with your unit for proper wire
terminations.

2.7.3.2 Remote Water Detector

Each remote water detector used will require two
conductors to be wired to the control terminal board
within the unit electrical box (see Figure 13). The wire
insulation must be rated at 600V. Refer to the electri-
cal schematic supplied with your unit for proper wire
terminations.

The number callouts in Figure 13 coincide with the
numbered items listed below:

  1.  Control I/O Board
    2.  Interface Terminals
  3.  Main Power Disconnect Switch
  4.  Ground Lug
  5.  Power Switches/Motor Start Protectors

 (Quantity varies by size of A/C unit)

  6.  Water Detector Circuit Board (Optional)
    7.  Transformer Circuit Breakers

CAUTION

 

Improper wire connections may result in the re-
verse rotation of the fans/blower motors and may
eventually result in damage to the unit. To cor-
rect this problem, exchange any two of the in-
coming main power wires at the main power dis-
connect switch. Do NOT rewire the unit's indi-
vidual components.

CAUTION

 

Prior to unit operation, an adequate unit-to-earth
ground must be connected to the unit.

4

1

3

5

2

6

7

Figure 13- Electric Box

Содержание Compact CW Series

Страница 1: ...Oct 2007 Compact CW Series Installation Operation Maintenance Manual Air Technology Systems Inc...

Страница 2: ...uage for use by anyone other than the owner of the equipment for which this manual is written without the prior written consent of Stulz Air Technology Systems Inc SATS This document contains confiden...

Страница 3: ...umidity Sensor 2 5 2 6 6 Remote Water Detector 2 6 2 7 Piping Connections 2 6 2 7 1 Chilled Water Hot Water 2 6 2 7 2 Condensate Drain 2 7 2 7 2 1 Gravity Drain 2 7 TABLE OF CONTENTS 2 7 2 2 Condensat...

Страница 4: ...Installation Downflow 2 2 Figure 7 Downflow Configuration TypicalAir Patterns 2 3 Figure 8 Upflow Configuration Typical Air Patterns Top Discharge 2 4 Figure 9 Upflow Configuration TypicalAir Patterns...

Страница 5: ...il at a rate that varies proportionally to the amount of cooling required to meet the user selectable tempera ture setpoint Heat from the surrounding air is trans ferred through the finned tubing of t...

Страница 6: ...nc s warranty does not cover failures caused by improper installation abuse misuse misapplication improper or lack of maintenance negligence accident normaldeterioration includingwearandtear ortheuseo...

Страница 7: ...le of supporting the unit When working on electrical equipment remove all jewelry watches rings etc Always disconnect the main power supply to the equipment at the main power disconnect switch before...

Страница 8: ...pply air as required to offset the sensible cooling of the system during the dehumidification cycle and for the automatic heating mode As a standard electric resis tance heating elements are factory i...

Страница 9: ...ller when a smoke alarm condition exists 1 6 3 Firestat Optionally mounted in the return air stream a fire detector senses high retun air temperature and signals the controller when a fire alarm condi...

Страница 10: ...d inside the air conditioner unless specified otherwise by the customer The filter box or plenum box assem bly if applicable is shipped separately Unpack and store these items in a safe place unless y...

Страница 11: ...ocated inside or outside the conditioned space but are designed to supply air to only one room The Compact CW systems are front accessible which allows the units to be placed in a corner or between ca...

Страница 12: ...as possible The return inlet is provided with a turned in flange on top of the unit for connection of the ductwork Refer to the installation drawing provided with the unit The connection of ductwork...

Страница 13: ...TLET RETURN AIR INLET Figure 8 Upflow Configuration Typical Air Patterns Top Discharge SUPPLY AIR OUTLET RETURN AIR INLET FRONT FREE RETURN REAR DUCTED RETURN Figure 9 Upflow Configuration Typical Air...

Страница 14: ...nsate pump may be provided for automatically eliminating condensate and humidifier flush water from the drain pan The conden sate pump is typically installed by the factory inside the A C unit If an o...

Страница 15: ...educed by the controller The user may also enter a gradient factor for humidity control Formula Newsetpoint oldsetpoint gradient startvalue actual value Example temperature 70 5 70 0 5 61 60 Example h...

Страница 16: ...freezing temperatures The diameter of the drain line should be the full size of the connection NOTE Pour some water into the condensate drain pan s prior to start up This fills the trap and prevents...

Страница 17: ...tions are required WARNING Verify power is turned off before making connec tions to the equipment NOTE All wiring must conform to local and national elec trical code requirements Use of copper conduc...

Страница 18: ...local and national electrical code requirements 2 7 3 1 Remote Temperature Humidity Sensor The remote temperature humidity sensor requires a three conductor shielded cable with the shield terminated a...

Страница 19: ...motor see Figure 14 is supplied with an adjustable sheave pulley to change blower speed and an adjustable base for belt tensioning Use the following procedure to change the blower speed 1 Turn the A...

Страница 20: ...cylinder is warm to verify if the humidifier is operational In all cases 1 to 6 hours might be required to see a desired level or rise in humidity in the conditioned space Once room conditions have b...

Страница 21: ...ing components as automatic con trols may start them unexpectedly 4 1 1 Compact CW Precision A C Unit 4 1 1 1 Filter The filter is usually the most neglected item in an air conditioning system To main...

Страница 22: ...A change cylinder light on the humidifier cabinet will illuminate red when the cylinder requires replacement NOTE The red light may illuminate during initial start up but it doesn t necessarily mean...

Страница 23: ...Low hot water flow Check hot water flow at supply source Inoperable Inspect piping for leaks or obstructions b Low hot water supply temperature Check hot water supply c Temperature setpoint too low In...

Страница 24: ...ing the Auto On Off Drain switch to the Drain position 4 4 3 When drained push the Auto On Off Drain switch to the Off position 4 Turn off power at the main power disconnect switch 5 The power wires t...

Страница 25: ...ges If you do not have established credit with SATS you must provide a freight carrier account number A written or faxed purchase order is required on warranty parts and must be received prior to 12 0...

Страница 26: ...Oct 2007 Air Technology Systems Inc Compact CW Series Installation Operation Maintenance Manual NOTES...

Страница 27: ...ith water 8 Water supply line connected to humidifier if required 9 Safety pan installed under ceiling mounted equipment if required 10 Filter box installed if required 11 Filter s installed if requir...

Страница 28: ...Oct 2007 Air Technology Systems Inc Compact CW Series Installation Operation Maintenance Manual...

Страница 29: ..._ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _...

Страница 30: ...Oct 2007 Air Technology Systems Inc Compact CW Series Installation Operation Maintenance Manual...

Страница 31: ...OB Freight on Board HACR Heating Air Conditioning Refrigeration HP Horse Power Hz Hertz IAQ IndoorAir Quality in w g Inches of Water Gauge KVA Kilo Volt Amps kW Kilowatt MAX CKT BKR Maximum Circuit Br...

Страница 32: ...Oct 2007 Air Technology Systems Inc Compact CW Series Installation Operation Maintenance Manual...

Отзывы: