EN/11.2016 © STULZ GmbH – all rights reserved
air side connection
If the air side has to be continued by a duct, the installation of a flexible connection is necessary.
Take into account the installation of pressure compensations in the flexible connection.
Adapter plate with damper or flexible connection
Knock-out openings for
supply connections
Bottom view
Unit front
- Connection under the unit
The adapter plate serves to attach a damper or a flexible connection under the unit. First install the actuator
onto the louver shaft on the right side (at the front construction size 1 and 2) looking at the unit front. Then fix
the louver with the actuator under the adapter plate. Now mount the adapter plate with pre-mounted louver on
the floor stand frame by means of bolts. Please take care that the adapter plate does not pass over the frame
to avoid canting of the floor stand within the raised floor.
The damper actuator, which is controlled via a 24 V signal by the controller, has to be electrically connected.
For this the delivered cable must be connected at the motor, be routed through an opening in the adapter
plate into the unit and then be connected at the controller in the electric box according to the electric diagram.
*for cabinet size 7
Cabinet size
Damper height for all units:
120 mm
Flexible connection height for all units: 150 mm
C / G
38
E/K
Содержание ASD series
Страница 4: ...4 4 EN 06 2017 G18D STULZ GmbH all rights reserved CYBERAIR 3PRO CW2 ORIGINAL INSTRUCTIONS...
Страница 38: ......
Страница 62: ...10 EN 11 2016 STULZ GmbH all rights reserved air side connection...
Страница 66: ...4 EN 05 2017 STULZ GmbH all rights reserved raised floor stand...
Страница 71: ...5 STULZ GmbH all rights reserved EN 04 2017 electrical opTIONS Wiring diagram of the circuit board...