STUDER INNOTEC

 

Users’ and Installers’ Handbook 

HPSI V2.0 E 

 page4 

 
 
 
 
The place where the inverter is to be mounted 
should meet the following requirements : 

 

  Out of reach of non authorised persons. 

  In a dry place with no condensation. 

  No inflammable material in the same room. 

  Not directly on top of the batteries. 

  Adequate  ventilation. Keep min. 10 cm 

distance to other object  

Air-flow path 

 
 

Connection 

Check the switch (4) is in “ OFF ” position. 
 
First  connect the 230V outlet (6) to the user 
device, so as to prevent any possible accidental 
contact. 
 

Check the tension and polarity of the 
battery ! 

The tension of the battery should coincide with 
that mentioned in the technical characteristics of 
the inverter. 
Battery connection :  

This connection should done be very 
carefully observing the polarity in order not 
to damage the device.

 

Check that the connections are fixed correctly. 

Use 

After connecting the inverter, make sure the 
user devices are correctly plugged in and that 
there is no possible contact between the “ Line 
OUT ” (6) and a person.  
 

The working device generates high tensions 
which could be fatal ! 
 
The inverter can be activated by moving the 
switch to the “ Auto ” position. The “ on ” 
indicator -green LED -(3) is illuminated. 

 

If no user device is connected, the LED blinks 
after some seconds, which indicates that the 
“ standby ” mode has started. If a user device is 
plugged in, the green LED remains illuminated, 
indicating the uninterrupted presence of 230V in 
the outlet. If you wish to deactivate the standby 
mode, put the switch in “ Lock ” position. The 
inverter will be then working continuously.  

 

Warning : 

With the “lock” mode, the no load 

consumption of the inverter is 15 to 20 

times greater ! 

Remote control 

The inverter can be controlled remotely with a 
switch (bi-stable) connected to the (5) 
connector on the Back side of the device. 
The main switch (4) has priority over the 
working mode of the device. If the remote 
switch is close, the inverter is out of use. 
 

Adjustments 

Standby Level (1) 

The activation of the inverter, when working in 
automatic mode, is dictated by the detection of a 
load. With this function, it is possible to adjust 
the minimum load detected between 0,3 and 20 
Watts. 

This level is factory adjusted to 2 

watts and so no further adjustment will 
probably be needed. 

Adjustment procedure 

Make sure that no device is connected. 
 
Check for the presence of hidden users such as 
television, fax, video, … which often have a 
standby mode and remain working even after 
being turned off ! 
 
Put the switch in “ Autom. ” position. 
Introduce a screw driver N°2 in the adjustment 
knob  (1) provided. 
Turn clockwise 

 until tight  

Wait until the green LED blinks. 

Ba

ck

si

de

F

ront

 s

ide

Top

Bottom

HPSI

Air 

flo

w

Содержание HPSI 2212

Страница 1: ...2 at Pnom Dynamic behaviour Normalization 0 5 ms for 0 to 100 load Frequency 50 Hz 0 01 Crystal control Charge detection User adjustable 0 5 to 20 W Maximum power load 15 min 1 3 1 6 x Pnom 25 C Maximum power load 3 min 1 6 2 x Pnom 25 C Peak power 5 sec 3 5 x Pnom Asymmetric charge Up to 2 x Pnom Cos φ max at Pnom 0 6 1 IP protection index IP 20 Forced ventilation From 45 C 3 C Overheating protec...

Страница 2: ...tallers Handbook HPSI V2 0 E page1 Sinewave inverter HPSI series User s and Installer s Handbook STUDER INNOTEC Rue des Casernes 57 CH 1950 Sion Tel 41 0 27 205 60 80 Fax 41 0 27 205 60 88 info studer inno com www studer inno com ...

Страница 3: ... 4 CONNECTION 4 USE 4 REMOTE CONTROL 4 Standby Level 1 4 Adjustment procedure 4 CONTROL 5 INDICATORS 5 Green Run LED 3 5 Red Fault LED 2 5 SAFETY 5 INTERNAL FUSE 5 ALARM CONTACT 5 MAINTENANCE 5 LEGISLATION 5 LIMITATION OF LIABILITY 5 DECLARATION OF CONFORMITY 7 EQUIVALENT CIRCUIT FOR HPSI INVERTER 8 DESCRIPTION AND WIRING DIAGRAM 9 TECHNICAL SPECIFICATIONS 10 ...

Страница 4: ...c network generator may be connected to the output of the inverter because this could result in its destruction As for the usage of batteries follow the manufacturer s instructions Important After disconnecting the battery the output tension 230V may still remain for 30 seconds The ventilation of the device should never be obstructed Should the device be installed in an enclosed structure make sur...

Страница 5: ...ected the LED blinks after some seconds which indicates that the standby mode has started If a user device is plugged in the green LED remains illuminated indicating the uninterrupted presence of 230V in the outlet If you wish to deactivate the standby mode put the switch in Lock position The inverter will be then working continuously Warning With the lock mode the no load consumption of the inver...

Страница 6: ...inverter after a failure put the switch 4 in OFF position for 10 seconds then connect again Safety The inverter is internally protected against overloads and short circuits Should this protection fail the inverter is equipped with a fuse fire protection If the fuse is broken qualified technicians should control the installation and change the fuse Internal fuse Fuse Inverter HPSI CF8 fuse links 30...

Страница 7: ...s with potential risks of serious harm to people or to the environment We do not accept any responsibility for any violation of patent rights or other third person rights resulting from the use of the inverter STUDER INNOTEC reserves the right to modify their products without previous notice ...

Страница 8: ...57 CH 1950 Sion Declares that the product Sinewave inverter Product Name HPSI Series Model Number HPSI 2212 HPSI 4424 HPSI 5048 Are conform to the following product specifications EN 50081 I II EN 55014 EN 55022 EN 50091 2 EN 60950 IEC 801 II III IV CEI 555 LVD 73 23 EEC EMC Dir 89 336 EEC Full name position Date Signature Roland Studer General director 16 02 2000 ...

Страница 9: ...blue wire and the yellow green wire This point can also be tied to ground if there is an existing ground Every ground point of appliances or plug should be tied together One side or the other of plus or minus battery input could also be tied to ground if needed A real neutral is an absolute need if there is a FI ground fault detector used as safety device In any case he installation of an inverter...

Страница 10: ...Inverter stop when contact is closed Main switch Run indicator Green LED Fault indicator red LED Standby level adjustment Not avalable with Twinpower option Battery connection Minus battery Alarm contact 60V 0 5A potential free 9 2 3 Check battery polarity Battery size sould be ajusted to the inverters power Cbatt Ah 5 x Pnom Unom This value could be divided by two for short time applications 6 ...

Страница 11: ...trol Charge detection User adjustable 0 3 to 20 W Maximum power charge 15 min 1 3n 1 6 x Pnom 25 C Maximum power charge 3 min 1 6 à 2 x Pnom 25 C Peak power 5 sec 3 5 x Pnom Asymmetric charge Up to 2 x Pnom Cos ϕ max at Pnom 0 6 1 IP protection index IP 20 Forced ventilation From 45 C to 3 C Overheating protection temperature 75 C 3 C Required battery capacity 5x Pnom Unom recommended value Acoust...

Отзывы: