TECHNICAL SPECIFICATIONS
Model:
HPSI
in box 19’’
2212
(HPSI)
4424
(HPSI)
5048
(HPSI)
Input voltage [Unom]
12V
24V
48V
Nominal power
2200W
4400W
5000W
Standby current
Power ON no load standby power
30
15W
35
<20W
30
<30W
Maximum
efficiency
91% 95% 95%
Height [HE] x depth [mm]
6U x 450
6U-337
9U-470
Weight
[kg]
35 51 57
Input voltage
< Unom x 0.95 - Unom x 1.33 >
Output voltage
Sinus 230 Vac (115Vac)
±
3%
Distortion
< 2% (at Pnom))
Dynamic behaviour
Normalisation 0.5 ms for 10% to 100% load
Frequency
50 Hz ± 0.01%(Crystal control)
Charge detection
User adjustable: 0.3 to 20 W
Maximum power charge 15 min.
1.3n – 1.6 x Pnom / 25°C
Maximum power charge 3 min.
1.6 à 2 x Pnom / 25°C
Peak power 5 sec.
3.5 x Pnom
Asymmetric charge
Up to 2 x Pnom
Cos
ϕ
max. at Pnom
0.6 – 1
IP protection index
IP 20
Forced ventilation
From 45°C to 3°C
Overheating protection temperature
75°C
±
3°C
Required battery capacity
> 5x Pnom/Unom (recommended value)
Acoustic level
Without ventilation : < 20 dB
With ventilation: < 45 dB
EEC conformity
EN 50081 I/II , EN 50014 - 50022
IEC 801 II / III / IV , CEI 555
Data are for information only and may change without notice
Other standard features:
. remote control possibility
. potential free alarm contact (60V/1A)
Options:
. HPSIxxxxTP
Twinpower system
. HPSIxxxxPE
3-phase for 3 x 400V systems