Studer Innotec SA
BSP
16
V1.0.3
User Manual
5. Quick Start guide
You will find in this chapter the procedure to follow in order to configure the BSP during installation. For the
major part of the systems this is good enough. For a full list of the parameters that can be set do refer to
Chapter 7.
5.1. Choosing the battery capacity
The battery capacity must be configured. The manufacturer gives it at various discharge times (see
Section 1.1.1). If several capacities at different times are supplied, the discharge time in 10 hours (C10) must
be choosen because these are the reference conditions for the state of charge calculation.
From the initial display of the RCC and by means of the keys UP and DOWN, move to the configuration menu
of the BSP parameters, then push SET.
To modify the parameter "Battery Capacity" {6001}, move with the arrows UP and DOWN to the general menu.
Then push on SET to enter the menu. With the arrow DOWN, move to the parameter "Battery Capacity".
To modify its value push on SET. The value turns in reverse vidéo.
Change the value for the one of your battery with the keys UP and DOWN. Confirm by pushing on SET.
Then, configure the parameter "Nominal Discharge Time(C-rating)" {6002} the same way as for the battery
capacity.