45
10.4.4 T
RANSPARENT
P
ARAMETER
–
P
There is a total of 31 parameters within the transparent parameter.
Each parameter is listed in the below table along with what they are set to as standard.
Index Description
Range
S-FX 70
S-FX 125
S-FX 220
S-FX 320
P01
Start Up Heat
Output
0
– 100%
30%
30%
30%
30%
P02
Heating Ramp
1-10c / minute
1-10c/min
1-10c/min
1-10c/min 1-10c/min
P03
Min Set Point
Temperature
20c
– 80c
20c
20c
20c
20c
P04
Heating Delay
Time
0
– 10 Minute
4 min
4 min
4 min
4 min
P05
CH Pump Over
Run
0
– 255 Minutes
3 min
3 min
3 min
3 min
P06
Pump Operation
0
– 3
0
0
0
0
P07
Min Modulating
Pump Speed
0
– 100%
30%
30%
30%
30%
P08
Modulating Pump
Start-Up Speed
0
– 100%
75%
75%
75%
75%
P09
Maximum Pump
Modulating Speed
0
– 100%
100%
100%
100%
100%
P10
Pump Shut Down
Temp in Overrun
0
– 100c
35c
35c
35c
35c
P11
Pump Start Up
Temp Hysteresis
0
– 100c
5c
5c
5c
5c
P12
Minimum Heating
Set Point
20
– 90c
20c
20c
20c
20c
P13
Maximum Heating
Set Point
20
– 90c
80c
80c
80c
80c
P14
Maximum Output
in CH Mode
0
– 100%
80%
80%
80%
80%
P15
DHW Ramp
1-10c / minute
5c / min
5c / min
5c / min
5c / min
P16
DHW Delay Time
0
– 255 Seconds
120
120
120
120
P17
DHW Pump
Overrun
0
– 255 Seconds
30
30
30
30
P18
Min DHW
Setpoint
With b02 set to 1, 4 or 7
With b02 set to 2,3,5,6,8 & 9
Not Used
10c
Not Used
10c
Not Used
10c
Not Used
10c
P19
Max DHW
Setpoint
With b02 set to 1, 4 or 7
With b02 set to 2,3,5,6,8 & 9
Not Used
65c
Not Used
65c
Not Used
65c
Not Used
65c
P20
Max Output in
DHW Mode
0-100%
80%
80%
80%
80%
P21
Storage Cylinder
Hysteresis
With b02 set to 1, 4 or 7
With b02 set to 2,3,5,6,8 & 9
Not Used
2c
Not Used
2c
Not Used
2c
Not Used
2c
P22
DHW Primary
Flow Temp
With b02 set to 1, 4 or 7
With b02 set to 2,3,5,6,8 & 9
Not Used
80c
Not Used
80c
Not Used
80c
Not Used
80c
P23
Legionella
Protection
With b02 set to 2,3,5,6,8 & 9
0 = Disabled ; 1 = Active
0
0
0
0
P24
Fan Freq in
Standby
0
– 255 Hz
0 Hz
0 Hz
0 Hz
0 Hz
P25
Modulating Pump
Control Temp
0
– 60c
35c
35c
35c
35c
P26
Primary Heat
Exchanger Dt
Protection
0
– 60c
35c
35c
35c
35c
P27
Min System PRV
Not Used
-
-
-
-
P28
Rated Sys PRV
Not Used
-
-
-
-
P29
Heat Exchanger
Protection
Activation
0 = No F43
1 = 1
– 15c / second
0
0
0
0
P30
Hysteresis in CH
mode start up
6
– 30c
10c
10c
10c
10c
P31
Hysteresis Timer
in CH mode start
60
– 180 Seconds
60 sec
60 sec
60 sec
60 sec