34
9.6.5
3
X
S-FX
IN CASCADE
:
1
X
D
IRECT HEATING CIRCUIT
&
1
X DHW PRIMARY CIRCUIT WITH PUMP
Legend
Required Parameter Changes
Every system requires different parameter settings, for the above system change the following parameters.
Master Boiler & Slave Boilers
Configuration Type:
-
Parameter
B02:
Set to 8 for 70, 125 & 320 models; Set to 5 for 220 model.
-
Parameter
B08:
Set to 3.
System Type:
-
Parameter
P.02:
Set to 1.
-
Parameter
P.09:
Set to 1
72
– Room Thermostat
138
– Outside Sensor
155
– DHW Tank Sensor
298
– Cascade Flow Temp Sensor
130
– DHW Primary Pump
306
– CH Heating Pump
300M
– Master Butterfly Valve
300S
– Slave Butterfly Valve