Example of PDU Usage Calculation
Rack Configuration Planning
5-5
In the calculations in
, components were added one by one, calculating:
The total current demanded by the components
The total space used in the rack
The total number of outlets required
In this example, two PDUs can provide enough current for two ftServer 2600, 4500, or
6300 systems, the LCD monitor unit, one tape drive (typical), and one
ftScalable Storage system. This set of components consumes 11.62 amperes; adding
another ftServer system would increase the consumption to 15.83 amperes, which
exceeds the 15 amperes limit for the PDUs. The configuration also utilizes 5 outlets in
the A-side PDU and 15U of rack space.
To add any more components, you require another pair of PDUs.
For information about planning a rack configuration, see:
“Determining PDU Requirements” on page 5-2
Содержание ftServer 2600
Страница 1: ...Stratus Technologies R638 02 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide...
Страница 8: ...Tables viii Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638...
Страница 44: ...Grounding Requirements 2 16 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638...
Страница 48: ...Planning for Cables 3 4 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638...
Страница 64: ...Example of PDU Usage Calculation 5 6 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638...
Страница 70: ...Monitor Requirements 6 6 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638...
Страница 80: ...AAP87600 PDU Specifications A 10 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638...
Страница 98: ...Index Index 4 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638...