USER MANUAL

CONTACT LIGHTING CONTROL PANEL

WWW. ST R A N D L I G H T I N G .CO M

7

To connect line/load wiring: 

Step 1. 

Install load and line wiring through knockouts. Refer to 

FIGURE 1 on page 3

 and 

FIGURE 4

 

below. 

Step 2. 

Connect proper grounding (

FIGURE 4

 

). 

Step 3. 

Install low-voltage wiring through knockouts. 

FIGURE 4. 

 LINE/LOAD WIRING CONNECTIONS 

NOTE: 

The 24-Circuit Panel is shown in this example, however, components are typical for all models. 

CONTROL WIRING 

Contact Lighting Control Panels may be controlled by the following methods: 

• DMX512 

• Vision.Net 

•  Optional ShowNet Ethernet (10/100BaseT) 

•  Auxiliary inputs: Panic Control or Fire Alarm Signal. 

•  Local control through Rack Control Module (RCM) processor. 

For approved wire types per control method, refer to “Appendix A: Standard Wiring” on page 22. 

Each Lighting Control Panel contains a Controller PCB for connection of control wiring. The Controller PCB also 
contains jumpers for termination of DMX512 signal and connection to Auxiliary panels. 

To connect control wiring: 

Step 1. 

Route control wiring from source to side of Lighting Control Panel.  

Step 2. 

Remove knockout(s) as required. See Figure 1 on page 5.  

Step 3. 

Install conduit fi ttings or insert lining materials in the knockout opening.  

Step 4. 

Pull control wiring through prepared openings.  

CAUTION:  

Wire openings must have fi ttings or linings to protect wire and cable insulation. 

Step 5. 

Prepare cabling as shown in “Appendix A: Standard Wiring” on page 22. 

Step 6. 

Connect wiring to appropriate locations on Controller PCB. See 

FIGURE 5 on page 8

Step 7. 

Set DMX A Thru termination jumper as required. 

TERMINAL TIGHTENING 

TORQUE 

Load/Line Circuit Wiring 

10 - 14 AWG 

350-600 kCM Torque @ 325 in-lbs 

Ground 

#4-14 Torque @ 45 in-lbs 

Relay Screw 

0.8 N-m to 1.2 N-m 

(Connection) 

Load

20 Amp (max) 
Branch Circuit 

Ground 
Connection 

Relay (24 single relays. Note, 2-pole relays occupy two slots.) 

Содержание 76910

Страница 1: ...12 CIRCUIT 24 CIRCUIT 36 CIRCUIT 48 CIRCUIT CONTACT LIGHTING CONTROL PANEL USER MANUAL...

Страница 2: ...Breakers 42 way For complete speci cations refer to Appendix B Speci cations on page 26 For Options and Accessories see Contact Options and Accessories on page 34 Please read all instructions before i...

Страница 3: ...TE The Contact 24 Circuit Panel is shown in this example however components are typical for all models Installation Operation Guide Contact Lighting Control Panel 2 OVERVIEW 7 FRONT PANEL 1 DETAIL A L...

Страница 4: ...277V FIGURE 2 LIGHTING CONTROL PANEL WITH INTERNAL CIRCUIT BREAKERS NOTE The 24 Circuit Breaker Panel is shown in this example however components are typical for all breaker models INSTALLATION OVERV...

Страница 5: ...at may be required for this installation Drill for mounting holes Pencil Wire stripper Digital voltmeter RMS Ratchet and assorted sockets Small at screwdriver Hammer for removing knockouts Knife Heat...

Страница 6: ...omponents are typical for all models CONNECTING LINE LOAD WIRING WARNING You must have access to a main circuit breaker or other power disconnect device before installing any wiring Be sure that power...

Страница 7: ...ler PCB for connection of control wiring The Controller PCB also contains jumpers for termination of DMX512 signal and connection to Auxiliary panels To connect control wiring Step 1 Route control wir...

Страница 8: ...Orange White Color White Orange Orange White Green Green White Blue Blue White Brown Brown Vision net Wiring Belden 1583A Pin No 1 2 3 4 5 6 7 8 9 Function Data Data Ground 24VDC Ground 24VDC Ground...

Страница 9: ...Escape button FIGURE 6 LCD MENU LED Status Indications LED CONDITION MEANING POWER Flashing Green Indicates power is active to the Rack Control Module RCM processor FAULT Flashing or Steady Red Indica...

Страница 10: ...nt N A Displays which preset a relay is assigned to Relay with Errors N A Displays the number of relays with an error Firmware N A Displays Processor s current firmware version as 86XXXX vX XX RELAY S...

Страница 11: ...ld take precedence unless the Primary source is not present at which time the Fallback source would take precedence Fallback vs Fallback in the this case the source with the highest level takes preced...

Страница 12: ...channels to specific relays TIME CLOCK FUNCTIONS SUB MENU OPTIONS COMMENTS View Current Events Press Enter to view scroll all programmed events Allows users to scroll through all programmed events Ad...

Страница 13: ...pli ed keypad addressing system using Vision Net button stations without the need of a computer Vision Net Designer not required When a keypad is in its Factory Default Mode its Room assignment can be...

Страница 14: ...station keypad and hold for three seconds The address is now assigned to that station Step 5 Walk to second Room where a button station is located Press any button on the station keypad and hold for t...

Страница 15: ...blinking off to indicate current relays assigned to that Room If a relay is not assigned to that Room its LED will not be illuminated Step 5 Once all relays are set as desired press Enter button to Sa...

Страница 16: ...see Event de ni tion above To Add an Action Step 1 At CLOCK CONFIG menu navigate to Add Edit Time Clock Events and press Enter button Step 2 At ADD NEW ACTION screen con gure action options Preset Ro...

Страница 17: ...ge parameters Use LEFT and RIGHT arrow button to navigate be tween parameters month day year Step 4 When all edits to Set Date are complete press Enter button to save con guration NOTE Pressing Escape...

Страница 18: ...ational Recognized Testing Laboratory Transfer Device To trigger the Contact Panel to enter the emergency mode a control signal Contact Closure open must be provided to the panel and connected to the...

Страница 19: ...drawing set if provided DO NOT convert these cables to home runs 5 DMX512 cable runs should all be in metal conduit Runs in exposed areas must be in metal conduit Maximum cable run should not exceed...

Страница 20: ...he loose conductors Step 6 Strip 1 8 inch of the insulation from each of the conductors Step 7 Terminate the conductors on the terminal block or solder the terminals as speci ed Step 8 For solder conn...

Страница 21: ...aximum length of any segment cable run including device cables between Hub or Switch and Node is 90 meters Maximum network diameter distance between any two Nodes is 180 meters MASTER AUXILIARY WIRING...

Страница 22: ...on Non Dim Fluo rescent HID LED Control via Internal Astronomical Timeclock Vision Net Control Stations Vision Net Occupancy Sensors Vision Net Photocells DMX512 ShowNet Operating Voltage Mix 120VAC 2...

Страница 23: ...Low Voltage Electronic Low Voltage Neon Non Dim Fluo rescent HID LED Control via Internal Astronomical Timeclock Vision Net Control Stations Vision Net Occupancy Sensors Vision Net Photocells DMX512...

Страница 24: ...c Low Voltage Electronic Low Voltage Neon Non Dim Fluo rescent HID LED Control via Internal Astronomical Timeclock Vision Net Control Stations Vision Net Occupancy Sensors Vision Net Photocells DMX512...

Страница 25: ...c Low Voltage Electronic Low Voltage Neon Non Dim Fluo rescent HID LED Control via Internal Astronomical Timeclock Vision Net Control Stations Vision Net Occupancy Sensors Vision Net Photocells DMX512...

Страница 26: ...g 14 000AIC 277VAC Load Types Incandescent Tungsten Halogen Magnetic Low Voltage Electronic Low Voltage Neon Non Dim Fluo rescent HID LED Control via Internal Astronomical Timeclock Vision Net Control...

Страница 27: ...ting 14 000AIC 277VAC Load Types Incandescent Tungsten Halogen Magnetic Low Voltage Electronic Low Voltage Neon Non Dim Fluo rescent HID LED Control via Internal Astronomical Timeclock Vision Net Cont...

Страница 28: ...Rating 14 000AIC 120VAC Load Types Incandescent Tungsten Halogen Magnetic Low Voltage Electronic Low Voltage Neon Non Dim Fluo rescent HID LED Control via Internal Astronomical Timeclock Vision Net Co...

Страница 29: ...Rating 14 000AIC 277VAC Load Types Incandescent Tungsten Halogen Magnetic Low Voltage Electronic Low Voltage Neon Non Dim Fluo rescent HID LED Control via Internal Astronomical Timeclock Vision Net Co...

Страница 30: ...PUT FOR 277V POWER SUPPLIES 1 2 3 Catalog Description 76931C Relay Insert Panel w Breakers 24 way 76932C Relay Insert Panel w Breakers 36 way 76933C Relay Insert Panel w Breakers 42 way CONTACT RELAY...

Страница 31: ...76990 Barrier Kit RELAY OPTIONS Catalog Description 76991 Relay 1 pole 76992 Relay 2 pole occupies two slots 347V POWER SUPPLY OPTION Catalog Description 76951 277 347V Power Supply for control electr...

Страница 32: ...P United Kingdom Tel 44 020 8965 3209 CONTACT LIGHTING CONTROL PANEL USER MANUAL DOCUMENT NUMBER 2 450330 010B VERSION DATE JULY 6 2020 2020 Signify Holding All rights reserved All trademarks are owne...

Отзывы: