USER MANUAL
CONTACT LIGHTING CONTROL PANEL
WWW. ST R A N D L I G H T I N G .CO M
7
To connect line/load wiring:
Step 1.
Install load and line wiring through knockouts. Refer to
FIGURE 1 on page 3
and
FIGURE 4
below.
Step 2.
Connect proper grounding (
FIGURE 4
).
Step 3.
Install low-voltage wiring through knockouts.
FIGURE 4.
LINE/LOAD WIRING CONNECTIONS
NOTE:
The 24-Circuit Panel is shown in this example, however, components are typical for all models.
CONTROL WIRING
Contact Lighting Control Panels may be controlled by the following methods:
• DMX512
• Vision.Net
• Optional ShowNet Ethernet (10/100BaseT)
• Auxiliary inputs: Panic Control or Fire Alarm Signal.
• Local control through Rack Control Module (RCM) processor.
For approved wire types per control method, refer to “Appendix A: Standard Wiring” on page 22.
Each Lighting Control Panel contains a Controller PCB for connection of control wiring. The Controller PCB also
contains jumpers for termination of DMX512 signal and connection to Auxiliary panels.
To connect control wiring:
Step 1.
Route control wiring from source to side of Lighting Control Panel.
Step 2.
Remove knockout(s) as required. See Figure 1 on page 5.
Step 3.
Install conduit fi ttings or insert lining materials in the knockout opening.
Step 4.
Pull control wiring through prepared openings.
CAUTION:
Wire openings must have fi ttings or linings to protect wire and cable insulation.
Step 5.
Prepare cabling as shown in “Appendix A: Standard Wiring” on page 22.
Step 6.
Connect wiring to appropriate locations on Controller PCB. See
FIGURE 5 on page 8
.
Step 7.
Set DMX A Thru termination jumper as required.
TERMINAL TIGHTENING
TORQUE
Load/Line Circuit Wiring
10 - 14 AWG
350-600 kCM Torque @ 325 in-lbs
Ground
#4-14 Torque @ 45 in-lbs
Relay Screw
0.8 N-m to 1.2 N-m
(Connection)
Load
20 Amp (max)
Branch Circuit
Ground
Connection
Relay (24 single relays. Note, 2-pole relays occupy two slots.)