Enable Door Sensor
The SCU is designed to support door sensors and for each door sensor, there are 3 possible configurations:
Option 1
. Door sensor and open alarm are enabled
This means the alarm will be sounded if:
The door is opened
without
a valid entry code being input (i.e. forced entry).
Door entry is governed by a strike timeout and the door is left open for more than the strike timeout time (even
if the door was opened by using a valid entry code). The alarm will stay on even if the door is subsequently
closed.
If the alarm is triggered because of either of these two events, it can be cancelled by either inputting a valid
engineer’s code, or by entering a valid entry code twice.
Option 2.
Door sensor is enabled and open alarm is disabled
This means the alarm will be sounded if:
The door is opened
without
a valid entry code being input (i.e. forced entry).
Door entry is governed by a strike timeout and the door is left open for more than the strike timeout time (even
if the door was opened by using a valid entry code). The alarm will stop when the door closes.
If the alarm is triggered because of forced entry, it can be cancelled by either inputting a valid engineer’s
code, or by entering a valid PIN code twice.
Option 0.
Door sensor and open alarm are both disabled
This means that no alarm will be sounded, regardless of how the door was opened or its status.
Please note: if the door sensor is enabled, then the door will relock whenever the door sensor is closed, irrespective of
the strike time set. This is to prevent ‘tailgating’.
1. To set up door sensors or to change their function,
first log into programming mode. The LED on keypad A will
flash red to indicate that they system is in programming mode and the buzzer on the controller will beep.
2. Press
‘6’.
3. Select which door sensor by pressing ‘1’ for door A or ‘2’ for door B.
4. Then select which configuration setting is required :- ‘0’, ‘1’ or ‘2’.
6. To log out of programming mode press ‘0’ or to continue programming, press the required programming
option number.