Para-
meter
Function description
Adjustment range
Standard
setting
Custom
setting
A31
Special function at boundary
alarm
0: no special function
1: buzzer
2: flashing display
3: flashing display and buzzer
4: like 3, buzzer can be
cancelled
5: like 4, cancelled buzzer
restarts after 10 min.
6: like 4, cancelled buzzer
restarts after 30 min
0
A32
Special function of upper
display
0: following value
1: setpoint
2: setpoint, if no differential
control
3: desired difference value, if
differential control
4: actual difference value
0
A33
Special function of lower
display
0: following value
1: setpoint
2: setpoint, if no differential
control
3: desired difference value, if
differential control
4: actual difference value
0
A34
Indication with function key 1,
if b1=2
0: leading value
1: desired difference value
2: actual difference value
1
A35
Type of setpoint S1‘ if b1=0
0: additive differential
temperature
1: alternate differential
temperature
2: freely adjustable setpoint
1
A40
Hysteresis mode contact K1
0: symmetrically
1: one-sided
0
A41
Hysteresis mode contact K2
0: symmetrically
1: one-sided
0
A42
Hysteresis mode alarm contact 0: symmetrically
1: one-sided
1
A60
Sensor type
4: Pt100 3-wire
5: PTC (KTY81-110)
6: 0...10 V, 0...20 mA
7: 2...10 V, 4...20 mA
4
A70
Software filter
0...10
(0 = inactive)
1
A80
Temperature scale
0: Fahrenheit (50 Hz)
1: Celsius (50 Hz)
2: Fahrenheit (60 Hz)
3: Celsius (60 Hz)
1
U1
Function output K1
0: no connection
1: connection to contact K1
2: connection to contact K2
3: connection to alarm contact
4: connection to ready message
1
Содержание ST48-WHDVM.04
Страница 2: ......