Second control level (P parameters):
Setting of control parameters
Simultaneously pressing the UP and DOWN key for at least 4 seconds opens a parameter list
containing control parameters. With the UP and DOWN keys the list can be scrolled in both
directions. Pressing the SET key will give you the value of the respective parameter. Pressing also
the UP or DOWN key at the same time the value can be adjusted.
Return to the initial position takes place automatically, if no key is pressed for 60 seconds.
Para-
meter
Function description
Adjustment range
Standard
setting
Custom
setting
P1
Setpoint 2 or
Delta W
-99 ... 999°C
-99 ... 99.9 K
+10.0 K
P2
Hysteresis contact K1
0.1 ... 99.9 K
1.0 K
P3
Hysteresis contact K2
0.1 ... 99.9 K
1.0 K
P4
Control range limitation –
minimum difference value
-99°C ... P5
-99°C
P5
Control range limitation –
maximum difference value
P4 ... 99,9°C
99,9°C
P7
Proportional band
0.1 ... 99.9 K
15.0 K
P8
Reset time Tn, I-factor
0...999 sec.
(0 sec. = inactive)
500 sec.
P9
Lead time Tv, D-factor
0...999 sec.
(0 sec. = inactive)
50 sec.
P10
Cycle time
2...100 sec.
8 sec.
P19
Key-lock
0: no key-lock
1: key-lock
0
P20
Following value display
-----
-----
P21
Following value correction
-10.0 ... 10.0 K
0.0 K
P22
Leading value display
-----
-----
P23
Leading value correction
-10.0 ... 10.0 K
0.0 K
P30
Lower limit value of the following
value for alarm contact
-99°C/K...P31
-10 K
P31
Upper limit value of the following
value for alarm contact
P30...999°C/K
+10.0 K
P32
Hysteresis alarm contact
0.1 ... 99.9 K
1.0 K
P33
Lower range limitation for fixed
setpoint control
-99 ... 999°C
-99°C
P34
Upper range limitation for fixed
setpoint control
-99 ... 999°C
999°C
P40
Analogue output
0: PID-control value (P43-P45)
1: following value (P41, P42)
2: leading value (P41, P42)
0
P41
Indication value for 0V at
analogue output
-99...999°C
0°C
P42
Indication value for 10V at
analogue output
-99...999°C
100°C
P43
Indication value full heating
performance (100%)
-10.0 ... +10.0 V
+10.0 V
P44
Indication value "0" performance
-10.0 ... +10.0 V
0.0 V
P45
Indication value full cooling
performance (100%)
-10.0 ... +10.0 V
0.0 V