Status messages
STATUS DISPLAY AND ERROR MESSAGES
Message
Cause
Remedy
Hi
Over-temperature,
temperature above alarm limit of parameter
A1
/
A31
Lo
Under-temperature,
temperature below alarm limit of parameter
A2
/
A33
E1L
Error on sensor F1, short-circuit
check sensor F1
E1H
Error on sensor F1, wire broken
check sensor F1
E2L
Error on sensor F2, short-circuit
check sensor F2
E2H
Error on sensor F2, wire broken
check sensor F2
E3L
Error on sensor F3, short-circuit
check sensor F3
E3H
Error on sensor F3, wire broken
check sensor F3
E4L
Error on sensor F4, short-circuit
check sensor F4
E4H
Error on sensor F4, wire broken
check sensor F4
E5
Door open for too long
close door
E6
High-pressure fault
Check: Condenser fan and check for dirt accumulation
E7
Low-pressure fault
Plant leaking, to little coolant
EP0
Internal error in control unit
Repair control unit
EP1
Error in parameter memory
Check all parameters
EP2
Error in data memory
Repair control unit
rtc
Error of internal clock
Set clock again. If error occurs again, the controller must
be repaired
The
EP0
and
EP1
errors disable the controller. The controller is not enabled until the error has been eliminated.
The error
EP0
(and
EP2
) can only be removed by repair.
The errors are displayed alternately with the currently measured temperature.