Order number: 900323.001 V1.74
Page 11
© Störk-Tronic 2021 • www.stoerk-tronic.com • Subject to modifications.
Parameter list software .112
H--
Temperature sensors
Para-
meter
Description of function
Setting range
Default
value
H1
Mains frequency
0: 50Hz
1: 60Hz
0
H11
Act. value sensor F1
Measured value, not adjustable
H12
Calibration sensor F1 (actual value correction)
-20...+20.0°C
0,0
H13
Weighting factor sensor F1
0.50...1.50
1,00
H14
Selection sensor F1
Depending on hardware, not all types are available.
Sensor will be deactivated in this case.
0: not existing
1: PTC
(-50..+150°C)
2: Pt100 2-wire (-100…+600°C)
3: Pt100 3-wire (-100…+500°C)
4: NTC
(-40…+40°C)
5: Pt1000 2-wire (-100…+330°C)
6: Pt1000 3-wire (-100…+300°C)
7: 0-20mA
8: 4-20mA
1
H15
Software filter sensor F1
1 .. 32
8
H16
Display at 0/4mA and sensor selection
H14
=7/8
-99..+999
0,0
H17
Display at 20 mA and sensor selection
H14
=7/8
-99..+999
100
H21
Act. value sensor F2
Measured value, not adjustable
H22
Calibration sensor F2 (act. value correction)
-20...+20,0°C
0,0
H23
Weighting factor sensor F2
0,50...1,50
1,00
H24
Selection sensor F2
see
H14
1
H25
Software filter sensor F2
1 .. 32
8
H26
Display at 0/4mA and sensor selection
H24
=7/8
-99..+999
0,0
H27
Display at 20 mA and sensor selection
H24
=7/8
-99..+999
100
H31
Act. value sensor F3
Measured value, not adjustable
H32
Calibration sensor F3 (act. value correction)
-20...+20,0°C
0,0
H33
Weighting factor sensor F3
0,50...1,50
1,00
H34
Selection sensor F3
see
H14
0
H35
Software filter sensor F3
1 .. 32
8
H36
Display at 0/4mA and sensor selection
H34
=7/8
-99..+999
0,0
H37
Display at 20 mA and sensor selection
H34
=7/8
-99..+999
100
H41
Act. value sensor F4
Measured value, not adjustable
H42
Calibration sensor F4 (act. value correction)
-20...+20,0°C
0,0
H43
Weighting factor sensor F4
0,50...1,50
1,00
H44
Selection sensor F4
see
H14
0
H45
Software filter sensor F4
1 .. 32
8
H46
Display at 0/4mA and sensor selection
H44
=7/8
-99..+999
0,0
H47
Display at 20 mA and sensor selection
H44
=7/8
-99..+999
100
H51
Display of weighted mean value of F1+F2
H51
= (
H53
*
H11
+ (100-
H53
)*
H21
)/100
H53
Weighting of sensor F1 for
H51
0 ... 100%
100
H99
Password of parameter level
H--
-99 ... 999
0