Relay contacts and lamps
(password-protected)
Para-
meter
Description of function
Setting range
Values
default
Function relay K1
0: no function (off)
1: compressor
2: defrosting circuit 1
3: evaporator fan
4: condenser fan
5: alarm
6: control contact circuit 2
7: defrosting circuit 2
8: relay function A (light 1)
9: relay function B (light 2)
10: relay function C (window heating)
11: relay function D (door frame heat.)
12: relay function E (blade scraper)
13: relay function F
14: drip tray heating
15: buzzer
16: on if controller active
17: on if control circuit 1 active
18: on if control circuit 2 active
19: on if Set 1 active
20: on if Set 2 active
21: on if day mode active
22: on if night mode active
1
Function relay K2
see
2
Function relay K3
see
3
Function relay K4
see
5
Function relay K5
see
0
Function relay K6
see
15
Function relay K7
see
0
Function relay K8
see
0