Temperature sensors
(password-protected)
Para-
meter
Description of function
Setting range
Values
default
Mains frequency
0: 50Hz
1: 60Hz
0
Act. value sensor F1
Measured value, not adjustable
Calibration sensor F1 (act. value correction)
-20...+20.0°C
0.0
Weighting factor sensor F1
0.50...1.50
1.00
Selection sensor F1
Depending on hardware, not all types are
available. Sensor will be deactivated in this
case.
0: not existing
1: PTC (-50..+150°C)
2: Pt100 2-wire (-100…+600°C)
3: Pt100 3-wire (-100…+500°C)
4: NTC (-40…+40°C)
5: Pt1000 2-wire (-100…+330°C)
6: Pt1000 3-wire (-100…+300°C)
7: 0-20mA
8: 4-20mA
1
Software filter sensor F1
1 ... 32
8
Display at 0/4mA and
sensor selection
=7/8
-99...+999
0.0
Display at 20 mA and
sensor selection
=7/8
-99...+999
100
Act. value sensor F2
Measured value, not adjustable
Calibration sensor F2 (act. value correction)
-20...+20.0°C
0.0
Weighting factor sensor F2
0.50...1.50
1.00
Selection sensor F2
see
1
Software filter sensor F2
1 ... 32
8
Display at 0/4 mA and
sensor selection
=7/8
-99..+999
0.0
Display at 20 mA and
sensor selection
=7/8
-99..+999
100
Act. value sensor F3
Measured value, not adjustable
Calibration sensor F3 (act. value correction)
-20...+20.0°C
0.0
Weighting factor sensor F3
0.50...1.50
1.00
Selection sensor F3
see
0
Software filter sensor F3
1 ... 32
8
Display at 0/4 mA and
sensor selection
=7/8
-99..+999
0.0
Display at 20 mA and
sensor selection
=7/8
-99...+999
100
Act. value sensor F4
Measured value, not adjustable
Calibration sensor F4 (act. value correction)
-20...+20.0°C
0.0
Weighting factor sensor F4
0.50...1.50
1.00
Selection sensor F4
see
0
Software filter sensor F4
1 ... 32
8
Display at 0/4 mA and
sensor selection
=7/8
-99…+999
0.0
Display at 20 mA and
sensor selection
=7/8
-99…+999
100