Monitoring and diagnosis on the inverter
Operation manual
ID 441896.05
WE KEEP THINGS MOVING
53
10
Indication of internal inverter diagnostic information on the EtherCAT interface
ECS 5000 and the connection to the EtherCAT. A text with the following format
is indicated in element 0: "
StX ErX L0X L1X
"
Part 1 of the text means:
St Abbreviation of EtherCAT Device State
State of the EtherCAT State Machine)
X Digit for state:
1 Init state
2 Pre-operaional state
(3 Requested bootstrap state wird nicht unterstützt)
4 Safe-operational state
8 Operational state
0x11 Error during INIT state
0x12 Error during PREOP state
(0x13 Error during BOOTSTRAP) state
0x14 Error during safe-operational state
0x18 Error during operational state
Part 2 of the text means:
Er Abbreviation of EtherCAT device error
X Digit for state:
0 No error
1 Booting error, ECS 5000 error
2 Invalid configuration, select configuration with EtherCAT in POSITool.
3 Unsolicited state change, inverter has changed state by itself.
4 Watchdog, no more data from EtherCAT even though timeout time
expired
5 PDI watchdog, host processor timeout
Part 3 of the text means:
L0 Abbreviation for LinkOn of port 0 (the RJ45 socket labeled "IN")
X Digit for state:
0 No link (no connection to other EtherCAT device)
1 Link detected (connection to other device found)
Part 4 of the text means:
L1 Abbreviation for LinkOn of port 1 (the RJ45 socket labeled "OUT")
X Digit for state:
0 No link (no connection to other EtherCAT device)
1 Link detected (connection to other device found)
Axis:
Global
Data type:
Str16
Value:
–
Index:
2101
hex
Subindex:
0
hex