A253.2 EtherCAT Sync Manager 2 PDO Assign
The Sync-Manager 3 controls the memory size and the access of the inverter
processor to the portion of memory in the EtherCAT Slave Controller (ESC) in
which the process input data with actual values are sent by the inverter to the
EtherCAT master. These data specify which PDO mapping parameters are
assigned to this Sync-Manager. This array contains four elements of the data
type U16. We recommend entering the value 0 (for unused) in element 2 of this
parameter because the indices of parameters
A233
(1A00
hex
) and
A234
(1A01
hex
) have already been entered as default values in elements 0 and 1. Up
to 12 parameters can already be transferred in this way. If more process data are
required, the CANopen
®
index of parameter A235 (1A02
hex
) can be specified
here. However, remember that the corresponding block 100922 ECS PDO3-rx
Map must also be instanced here.
Axis:
Global
Data type:
U16
Value:
0 ... 0000
hex
... 65535 (representation hexadecimal)
Index:
20FD
hex
Subindex:
2
hex
A253.3 EtherCAT Sync Manager 3 PDO Assign
The Sync-Manager 3 controls the memory size and the access of the inverter
processor to the portion of memory in the EtherCAT Slave Controller (ESC) in
which the process input data with actual values are sent by the inverter to the
EtherCAT master. These data specify which PDO mapping parameters are
assigned to this Sync-Manager. This array contains four elements of the data
type U16. We recommend entering the value 0 (for unused) in element 3 of this
parameter because the indices of parameters
A233
(1A00
hex
) and
A234
(1A01
hex
) have already been entered as default values in elements 0 and 1 and
sometimes the index of
A235
(1A03
hex
) in element 2. Up to 18 parameters can
already be transferred in this way. If more process data are required, the
CANopen
®
index of parameter
A236
(1A03
hex
) can be specified here. However,
remember that the corresponding block 100924 ECS PDO4-tx Map must also be
instanced here.
Axis:
Global
Data type:
U16
Value:
0 ... 0000
hex
... 65535 (representation hexadecimal)
Index:
20FD
hex
Subindex:
3
hex