Mechanical Installation
ID 441689.03
10
Operating manual Axis switch POSISwitch® AX 5000
4
WE KEEP THINGS MOVING
4
Mechanical Installation
This chapter gives you complete information on the subject of mechanical installation. Only specialized
personnel qualified for this task may instal, commission and control the device.
4.1
Installation Location
•
Operate only in closed switching cabinet.
•
Avoid installation above heat-generating devices.
•
Ensure sufficient air circulation in the switching cabinet. (The installation site of POSISwitch® AX 5000
may not hinder the air circulation of the inverter).
•
The installation site must be free of dust, corrosive fumes and all liquids (in accordance with soil degree
2 as per EN 50178).
•
Avoid humidity.
•
Avoid condensation (e.g., due to anti-condensation heaters.
•
To satisfy EMC requirements, use mounting plates with conductive surfaces (e.g., unpainted).