On/off heating
If the heating consists of on/off (non-modulating) heating, you can call up the operating hours of the heating. In
addition to today's operating hours, the operating hours of the past 7 days and the total number of operating
hours are shown as well.
Enter “yes” behind “Clear running hours” to erase the operating hours of the heating displayed.
COOLING
To prevent the humidity in the house from becoming too high due to cooling, the cooling can be switched off by
the RH. If the relative humidity rises to above the preset value, the cooling will be switched off.
Soaking
If the house is
not in use,
you can use the “Soaking” function to run the cooling system at full capacity (ON or
100%) for the “Cycle time on”. As soon as the house status changes, “Soaking” will be switched “off” to prevent
the soaking starting immediately after you switch the house to “not in use”.
In addition, if
modulating cooling
is used, this screen lets you set the cycle time.
On/off cooling
If the cooling consists of on/off (non-modulating) cooling, you can call up the operating hours of the cooling. In
addition to today's operating hours, the operating hours of the past 7 days and the total number of operating
hours are shown as well.
Enter “yes” behind “Clear running hours” to erase the operating hours of the cooling.
MISCELLANEOUS CONTROLS
Pressure control
Controlling the flaps on the basis of a preset underpressure guarantees an optimum flow pattern for the
incoming air.
The pressure setting and the current pressure measured are used to determine the “Calc. ventilation press.”.
The pressure controlled flaps are readjusted every 2 minutes (gradual control). At large deviations between
setting and current pressure it can take some time before the flaps have reached the calculated position. By
changing the "calculated ventilation pressure" value you can speed up the settling time for the flaps.
External input
Items such as the status of the hatches that provide access to an open-air run can be connected to the external
input. The openings of these hatches enable a lot of cold air to enter the house which causes a significant drop
in the house temperature, specifically at the bottom of the house. If the pressure control was not switched off,