iNSTallaTiON
installation
12 |
WSP-2-DUO, WSG-2-DUO
Removing the casing door
f
f
Open the latch of the casing door.
f
f
Tilt the casing door forwards. lift the rebate of the casing
door from the frame.
10.1.4 Installation on unfinished walls
The casing for unfinished walls – available as an accessory – is
set into the wall. The appliance is installed in the casing after
it has been plastered in.
Removing the casing door and frame
f
f
Open the latch of the casing door.
f
f
Tilt the casing door forwards. lift the rebate of the casing
door from the frame.
f
f
Undo the four screws inside the corners of the casing for
unfinished walls.
f
f
remove the frame.
Installing the casing for unfinished walls
170
390
576
118
102
80
D
00000
75
07
1
The minimum clearance (80 mm) refers to the clearance from
the floor covering, allowing for any skirting boards. if no skirt-
ing boards or narrower ones will be used, the clearance can be
reduced to a minimum of 20 mm.
f
f
Create a wall recess with the specified dimensions (see
chapter "Specification / Dimensions and connections").
f
f
Set the casing for unfinished walls into the wall recess.
f
f
Secure the casing for unfinished walls using suitable
screws (not part of the standard delivery). if setting the
casing for unfinished walls into a drywall, the fixing tabs
of the casing can be used as installation aids.
f
f
align the casing.
D
00000
75
19
0
f
f
Guide the appliance onto the hooks in the casing. Use the
rectangular recesses.
f
f
Tighten the screw connection between the appliance
and the mounting rail or heating circuit distributor (for
torque, see chapter "Specification / Dimensions and
connections").
f
f
Connect the mounting rail or heating circuit distributor to
the pipework with flat gaskets.
10.2 Water connection
!
Material losses
Dirt and sludge can accumulate in the appliance and
cause overheating, noise, corrosion and faults in the
appliance.
f
f
Thoroughly flush the heating system before con-
nection.
f
f
route the pipework up to the appliance.
f
f
Connect the pipework to the shut-off valve of the appli-
ance ensuring that it is stress-free.
f
f
Check the correct position of the shut-off valves.
10.3 Electrical connection
WARNING Electrocution
Before any work on the appliance, ensure omnipolar
disconnection from the power supply.
Note
Observe the operating and installation instructions for
the integral instantaneous water heater.
f
f
route the electrical connections into the appliance.
f
f
incorporate the appliance in the equipotential bonding.
Use the connection at the bottom left-hand section of the
mounting plate (min. 6 mm
²
CU).