![STIEBEL ELTRON WPSF Скачать руководство пользователя страница 7](http://html1.mh-extra.com/html/stiebel-eltron/wpsf/wpsf_installation-manual_1376766007.webp)
InstallatIon
Installation
WPsF
| 7
ENGL
IS
H
5. Installation
5.1 Fitting the drain hose
f
f
Fit the drain hose supplied to the safety valve.
f
f
size the drain hose so that brine can drain off unimpeded
when the safety valve is fully opened.
f
f
lay the safety valve drain hose with a constant fall to the
drain.
f
f
Ensure that the safety valve drain hose is open to the
outside.
5.2 Charging the heat source system
D
00000
384
22
1
2
3
4
5
1 shut-off valve, heat source flow
2 Quick-action air vent valves
3 shut-off valve, heat pump flow
4 Filling
5 Drain
f
f
Close the shut-off valve in the heat source flow.
f
f
open the shut-off valve in the heat pump flow.
f
f
Connect the refrigerant flow line to the charging side of
the unit.
f
f
Connect the refrigerant return line to the draining side of
the unit.
f
f
Carry out a pressure test. Remove the safety valve and in-
sert the plug supplied.
4.
3.
1.
2.
D
00000
38
15
7
1
2
1 safety valve
2 Plug
f
f
Check for tightness.
f
f
Charge the heat source system to the required operating
pressure. For this, observe the maximum operating pres-
sure (see chapter “specification / Data table”)
f
f
Close the shut-off valve in the heat pump flow.
f
f
Remove the plug and refit the safety valve.
f
f
Vent the heat source system via the quick-action air vent
valve.
f
f
after venting, close the quick-action air vent valve.
5.3 Removing the strainer
If there is a high pressure drop in the heat source system, you
can remove the strainer in the filter chamber of the product
(see chapter “specification / Pressure drop diagram”).
!
Material losses
f
f
For opening and closing the filter chamber, use
exclusively the hook wrench supplied.
1
2
D
00000
38
15
5
1 strainer
2 Filter cartridge
f
f
open the filter chamber. Remove the filter cartridge.
f
f
Remove the strainer from the heat pump flow.
f
f
Re-insert the filter cartridge. Close the filter chamber.
f
f
tighten the cover with a torque of 15 nm.
f
f
open the shut-off valves in the heat source flow and the
heat pump flow.
f
f
Vent the heat source system via the quick-action air vent
valve.
f
f
after venting, close the quick-action air vent valve.
6. Maintenance
f
f
Clean the filter cartridge if required.