INSTALLATION
Appendix
www.stiebel-eltron.com
WPE-I H 400 Premium |
85
EN
GL
ISH
Message
Class
Description
Heating circuit 2 control
C
Temperature deviation in accordance with alarm settings for distributor circuit 2
Heating circuit 3 control
C
Temperature deviation in accordance with alarm settings for distributor circuit 3
Heating circuit 4 control
C
Temperature deviation in accordance with alarm settings for distributor circuit 4
Heating circuit 5 control
C
Temperature deviation in accordance with alarm settings for distributor circuit 5
WCS control
C
Temperature deviation in accordance with alarm settings for WCS
Cooling circuit flow control
C
Temperature deviation in accordance with alarm settings for cooling
Cooling control
C
Temperature deviation in accordance with alarm settings for cooling cylinder
Control, surplus heat
C
Temperature deviation in accordance with alarm settings for surplus heat
Room temperature sensor
C
Room sensor communication error
External alarm
C
Alarm input for external alarm; activation in the menu “Alarm control/central alarm” menu is
required
Low system flow temperature
C
Flow temperature below 70 % of the set value for longer than 3 hours
High system supply temp.
C
Flow temperature exceeds the specified limit value (standard: 70 °C)
Error comm. to primary
D
Communication error secondary to primary heat pump
Error comm. to secondary
D
Communication error primary to secondary heat pump
Too few secondary pumps found
D
The number of secondary heat pumps communicating with the primary heat pump is less than
expected
Secondary pump class A
D
A secondary heat pump reacting to a class A alarm
Secondary pump class B
D
A secondary heat pump reacting to a class B alarm
Alarm, ext. heat pump pressure switch
E
Operating pressure switch for extension module
Ext. heat pump general error
E
Central alarm from secondary heat pump
Ext. heat pump communication
E
Communication error extension module (to primary heat pump)