GAS PIPING

 To avoid damage or possible personal injury, do not connect gas piping to this unit

until a supply line pressure/leak test has been completed. Connecting the unit before completing the
pressure/leak test may damage the unit gas valve and result in a fire hazard.
Do not rely on a shut-off valve to isolate the unit while conducting gas pressure/leak tests. These
valves may not be completely shut off, exposing the gas valve to excessive pressure and damage.

NOTICE: If more than one unit heater is to be served
by the same piping arrangement, the total cu. ft./hr.
input and length of pipe must be considered.

NOTICE: If the gas unit heater is to be fired with LP
gas, consult your local LP gas dealer for pipe size
information.

NOTICE: HEATER INSTALLATION FOR USE WITH
PROPANE  (BOTTLED) GAS MUST BE MADE BY A
QUALIFIED L.P. GAS DEALER OR INSTALLER.  HE/
SHE WILL INSURE THAT PROPER JOINT
COMPOUNDS ARE USED FOR MAKING PIPE
CONNECTIONS; THAT AIR IS PURGED FROM
LINES; THAT A THOROUGH TEST IS MADE FOR
LEAKS BEFORE OPERATING THE HEATER; AND
THAT IT IS PROPERLY CONNECTED TO THE
PROPANE GAS SUPPLY SYSTEM.

Before any connection is made to the existing line
supplying other gas appliances, contact the local gas
company to make sure that the existing line is of
adequate size to handle the combined load.

1.  Determine the required Cu. Ft./Hr. by dividing the input  by 1000.  For SI/Metric measurements: Convert BTU/Hr. to kilowatts.  Multiply the
units inputs (kW) by 0.0965 to determine Cu. Meters./Hr. 2. FOR NATURAL GAS: Select pipe size directly from the table. 3. FOR PROPANE
GAS: Multiply the Cu. Ft./Hr. value by 0.633; then, use the table.  4. Refer to the metric conversion factors listed in the General Safety section
for SI Unit measurement conversions.

Maximum Capacity of Pipe in Cubic Feet of Gas per Hour (Cubic Meters per Hour) for Gas Pressures of 0.5 psig (3.5 kPa) or Less,

and a Pressure Drop of 0.5 Inch Water Column (124.4 Pa)

(Based on a 0.60 Specific Gravity Gas)

Nominal

Iron

Internal

Length of Pipe,  Feet (meters)

Pipe Size

Dia.

10

20

30

40

50

60

70

80

90

100

125

150

175

200

in.

in.

(3.0)

(6.1)

(9.1)

(12.2)

(15.2)

(18.3)

(21.3)

(24.4)

(27.4)

(30.5)

(38.1)

(45.7)

(53.3)

(61.0)

 1/2

0.622

175

120

97

82

73

66

61

57

53

50

44

40

37

35

(4.96)

(3.40)

(2.75)

(2.32)

(2.07)

(1.87)

(1.73)

(1.61)

(1.50)

(1.42)

(1.25)

(1.13)

(1.05)

(0.99)

 3/4

0.824

360

250

200

170

151

138

125

118

110

103

93

84

77

72

(10.2)

(7.08)

(5.66)

(4.81)

(4.28)

(3.91)

(3.54)

(3.34)

(3.11)

(2.92)

(2.63)

(2.38)

(2.18)

(2.04)

1

1.049

680

465

375

320

285

260

240

220

205

195

175

160

145

135

(19.3)

(13.2)

(10.6)

(9.06)

(8.07)

(7.36)

(6.80)

(6.23)

(5.80)

(5.52)

(4.96)

(4.53)

(4.11)

(3.82)

1 1/4

1.380

1400

950

770

660

580

530

490

460

430

400

360

325

300

280

(39.6)

(26.9)

(21.8)

(18.7)

(16.4)

(15.0)

(13.9)

(13.0)

(12.2)

(11.3)

(10.2)

(9.20)

(8.50)

(7.93)

1 1/2

1.610

2100

1460

1180

990

900

810

750

690

650

620

550

500

460

430

(59.5)

(41.3)

(33.4)

(28.0)

(25.5)

(22.9)

(21.2)

(19.5)

(18.4)

(17.6)

(15.6)

(14.2)

(13.0)

(12.2)

2

2.067

3950

2750

2200

1900

1680

1520

1400

1300

1220

1150

1020

950

850

800

(112)

(77.9)

(62.3)

(53.8)

(47.6)

(43.0)

(39.6)

(36.8)

(34.5)

(32.6)

(28.9)

(26.9)

(24.1)

(22.7)

2 1/2

2.469

6300

4350

3520

3000

2650

2400

2250

2050

1950

1850

1650

1500

1370

1280

(178)

(123)

(99.7)

(85.0)

(75.0)

(68.0)

(63.7)

(58.0)

(55.2)

(52.4)

(46.7)

(42.5)

(38.8)

(36.2)

3

3.068

11000

7700

6250

5300

4750

4300

3900

3700

3450

3250

2950

2650

2450

2280

(311)

(218)

(177)

(150)

(135)

(122)

(110)

(105)

(97.7)

(92.0)

(83.5)

(75.0)

(69.4)

(64.6)

4

4.026

23000

15800

12800

10900

9700

8800

8100

7500

7200

6700

6000

5500

5000

4600

(651)

(447)

(362)

(309)

(275)

(249)

(229)

(212)

(204)

(190)

(170)

(156)

(142)

(130)

Table 3 - Gas Pipe Size

PIPE SIZING

To provide adequate gas pressure to the gas unit heater,
size the gas piping as follows:

1. Find the cu. ft./hr. by using the following formula:

       Input BTU/Hr.

Cu. ft./hr. =

              1000

2. Refer to Table 3.  Match “Length of Pipe in Feet”

with appropriate “Gas Input - Cu. Ft./Hr.” figure.
This figure can then be matched to the pipe size at
the top of the column.
Example:
It is determined that a 67 foot (20.4m) run of gas
pipe is required to connect a 200 MBTU gas unit
heater to a 1,000 BTU/cu ft. (0.29kW) natural gas
supply.

200,000 BTU/Hr

                                    = 200 Cu. ft./hr.

1,000 BTU/cu. ft.

Using Table 3, a 1 inch pipe is needed.

NOTE: See General Safety Information section for
English/Metric unit conversion factors.

Содержание TUBULAR GAS FIRED PROPELLER UNIT HEATERS

Страница 1: ...that these substances may cause cancer birth defects or other reproductive harm INSTALLER S RESPONSIBILITY Installer Please Note This equipment has been test fired and inspected It has been shipped f...

Страница 2: ...6 Proper Clearances 5 6 Suspension of Units 5 6 Gas Piping 7 8 ELECTRICAL CONNECTIONS 9 10 11 12 13 VENTING 14 15 16 17 18 OPERATION Explanation of Controls and Operation 19 Main Burner Orifice Sched...

Страница 3: ...rocedures listed on Gas Equipment Start Up Sheet located in this manual Use only the fuel for which the heater is designed see rating plate Using LP gas in a heater that requires natural gas or vice v...

Страница 4: ...8 5 8 48 5 8 473 473 473 778 778 778 1235 1235 1235 F Discharge Opening Width 18 3 4 18 3 4 18 3 4 30 3 4 30 3 4 30 3 4 48 3 4 48 3 4 48 3 4 476 476 476 781 781 781 1238 1238 1238 G Depth to CL Flue 4...

Страница 5: ...epair Garages In Canada installation must be in accordance with current CGA B149 Installation Codes for Gas Burning Appliances and Equipment AIR DISTRIBUTION Direct air towards areas of maximum heat l...

Страница 6: ...acent materials Make certain that the lifting methods used to lift the heater and the method of suspension used in the field installation of the heater are capable of uniformly supporting the weight o...

Страница 7: ...ity Gas Nominal Iron Internal Length of Pipe Feet meters Pipe Size Dia 10 20 30 40 50 60 70 80 90 100 125 150 175 200 in in 3 0 6 1 9 1 12 2 15 2 18 3 21 3 24 4 27 4 30 5 38 1 45 7 53 3 61 0 1 2 0 622...

Страница 8: ...test edition National Fuel Gas Code in Canada according to CGA B149 See Tables 1 3 for correct gas piping size If gas pressure is excessive on natural gas applications install a pressure regulating va...

Страница 9: ...n cause severe personal injury or death Standard units are shipped for use on 115 volt 60 hertz single phase electric power The motor name plate and electrical rating of the transformer should be chec...

Страница 10: ...Units Equipped with Hot Surface Pilot Single Stage 100 400 Unit Sizes with Natural Gas and Propane LP Gas Figure 5d Primary HWSV9540 SV9640 Hot Surface Ignition Gas Controls Figure 5e Alternate HWSV95...

Страница 11: ...11 ELECTRICAL CONNECTIONS continued Figure 5f Tubular Units Equipped with S8600 Single Stage Ignition Optional for Tubular 100 400 Unit Sizes with Natural Gas and Propane LP Gas...

Страница 12: ...12 ELECTRICAL CONNECTIONS continued Figure 5g Tubular 100 400 Unit Sizes with Optional 2 Stage Ignition...

Страница 13: ...s in areas under negative pressure due to large exhaust fans or air conditioning When required a flue vent fan should be installed in accordance with the instructions included with the fan 10 Vent con...

Страница 14: ...hall terminate at least four feet 1 2m below four feet 1 2m horizontal from or one foot 0 3m above any door window or gravity vent air inlet into the building The vent terminal must be at least 12 inc...

Страница 15: ...l codes with current CGA B149 1 Installation Codes for Natural Gas Burning Appliances and Equipment or CGA B149 2 Installation Codes for Propane Gas Burning Appliances and Equipment 2 Any reference to...

Страница 16: ...16 Figure 8A Figure 8B VENTING continued...

Страница 17: ...17 VENTING continued Figure 9A Figure 9B...

Страница 18: ...wall thermostat supplied optionally is a temperature sensitive switch which operates the vent system and the ignition system to control the temperature of the space being heated It must be mounted on...

Страница 19: ...unit heaters must be orificed to 90 of the normal altitude rating and be so marked in accordance with CSA certification Check the gas input rate as follows Refer to General Safety Information section...

Страница 20: ...ssure altitude of the unit installation and the technician s name and date on the label using a permanent marker Refer to Installation Instruction section on Adjustments Gas Input Rate for adjusting t...

Страница 21: ...ssure Refer to Operation Replace regulator section of combination gas valve or complete valve Check with local gas supplier for proper orifice size and replace Refer to Operation 1 Clean main burner p...

Страница 22: ...ration 3 Purge air from gas line 4 Follow lighting instruction label adjacent to gas valve 5 Remove pilot orifice Clean with compressed air or solvent Do not ream 6 Refer to Operation 7 Check thermoco...

Страница 23: ...cal Connections 2 Replace motor 3 Check for 24V across 1 and 3 terminals on fan relay If 24V is present jumper terminals numbered 2 and 4 If motor runs the relay is defective and must be replaced If 2...

Страница 24: ...will be free from defects in material or workmanship for 1 year from the date of shipment from the factory or one and one half 1 1 2 years from the date of manufacture whichever occurs first The Manuf...

Страница 25: ...the heat exchanger 5 Remove any dirt dust or other foreign matter from the burners using a wire brush and or compressed air Ensure that all parts are unobstructed Inspect and clean the pilot burner i...

Страница 26: ...FICATION OF PARTS PROPELLER UNIT HEATERS Figure 13 Heat Exchanger Assembly Figure 14 Electrical Control Panel Figure 11 Propeller Parts Figure 12 Component Parts D4430 Fan Guard Fan Blade Hardware Har...

Страница 27: ...er Assembly 300 400 Unit Sizes Shown HOW TO ORDER REPLACEMENT PARTS Please send the following information to your local representative if further assistance is needed contact the manufacturer s custom...

Страница 28: ...and all the controls on this equipment If not contact your wholesaler or rep DO NOT START this equipment unless you fully understand the controls GAS EQUIPMENT START UP GENERAL With power and gas off...

Отзывы: