INSTALLATION (continued)
CLEARANCES:
Each Gas Unit Heater shall be located
with respect to building construction and other equipment
so as to permit access to the Unit Heater. Clearance
between vertical walls and the vertical sides of the Unit
Heater shall be no less than 6 inches (152mm).
However, to ensure access to the control box, a
minimum of 18" (457mm) is required for the control box
side. A minimum clearance of 6 inches (152mm) must
be maintained between the top of the Unit Heater and
the ceiling. The bottom of the Unit Heater must be no
less than 12 inches (305mm) from any combustible.
The distance between the flue collector and any
combustible must be no less than 6 inches (152mm).
Also see AIR FOR COMBUSTION and VENTING
sections.
NOTICE: Increasing the clearance distances may
be necessary if there is a possibility of distortion or
discoloration of adjacent materials.
Make certain that the lifting
methods used to lift the heater and the method
of suspension used in the field installation of
the heater are capable of uniformly supporting
the weight of the heater at all times. Failure to
heed this warning may result in property damage
or personal injury!
Make sure that the structure to
which the unit heater is to be mounted is capable
of safely supporting its weight. Under no
circumstances must the gas lines, the venting
system or the electrical conduit be used to
support the heater; or should any other objects
(i.e. ladder, person) lean against the heater gas
lines, venting system or the electrical conduit
for support. Failure to heed these warnings may
result in property damage, personal injury, or
death.
Unit Heaters must be hung level from
side to side and from front to back, see Figure 3A,
3B and 3C. Failure to do so will result in poor
performance and /or premature failure of the unit.
Insure that all hardware used in
the suspension of each unit heater is more than
adequate for the job. Failure to do so may result
in extensive property damage, severe personal
injury, or death!
Refer to Figures 3A, 3B and 3C for suspension of units.