No Cycling or appliance power
or thermostat call for heat
since appliance failure has
occured.

Line voltage power can
cause product damage,
severe injury or death.
Only a trained experienced
service technician should
perform this trouble-
shooting.

1. Check the system thermo-

stat to make sure it is call-
ing for heat. (Do not cycle
the thermostat on and off
at this time.)

2. Remove the appliance

burner compartment door.
Do not interrupt power to
the SV9540; SV9640 by
opening any electrically
interlocked panels.

3. Observe the LED indicator

on the SV9540; SV9640;
check and repair system as
noted in the chart to the
right.

Table 6 - Tubular Propeller Trouble Shooting with LED Indicator Assistance

1. Line voltage input power at L1

and L2 connector.

2. Low voltage (24V) power at 24

VAC and COM.

3. System wiring harness is in good

condition and securely connected
at both ends.

Not Applicable

1. Ignition system control switch

must be in the ON position.

2. Airflow proving switch operation,

tubing and wiring.

3. Obstructions or restrictions in

appliance air intake or exhaust
flue system that prevent proper
combustion airflow.

1. Open manual reset or auto reset

burner rollout switch.

2. Open high temperature or

auxiliary limit switch.

3. Replace venter relay.

1. Gas supply off or at too low

pressure to operate appliance.

2. Damaged or broken HSI element.
3. Line voltage HOT lead wire not

connected to L1 terminal (check
polarity)

4. Appliance not properly earth

grounded.

5. Flame sense rod contaminated or

in incorrect location.

6. Be sure pilot burner lead wires are

in good condition and properly
connected.

No power to system control

Normal operation
This indication shows whenever the
system is powered, unless some
abnormal event has occurred.

Airflow proving switch remains
open longer than 30 seconds after
combustion air blower energized

System goes into 5-minute delay
period, with combustion air blower off.
At the end of the 5-minute delay,
another ignition cycle will begin.

Limit string is open.

System Lockout
After 5-minute delay time, control
system will reset and initiate a new
ignition sequence, if the call for heat
is present.

LED STATUS

INDICATES

CHECK/REPAIR

Off

Bright – Dim

3 Flashes

4 Flashes

6 Flashes

LIMITED WARRANTY

Power Vented Tubular Propeller Unit Heaters

1. The "Manufacturer" warrants to the original owner at original

installation site that the above model Gas-Fired Heater ("the
Product") will be free from defects in material or workmanship for
(1) year from the date of shipment from the factory, or one and
one-half (1-1/2) years from the date of manufacture, whichever
occurs first. The Manufacturer further warrants that the complete
heat exchanger, and burners be free from defects in material or
workmanship for a period of ten (10) years from the date of
manufacture. If upon examination by the Manufacturer the Product
is shown to have a defect in material or workmanship during the
warranty period, the manufacturer will repair or replace, at its
option, that part of the Product which is shown to be defective.

2. This limited warranty does not apply:

a. if the product has been subjected to misuse or neglect, has

been accidentally or intentionally damaged, has not been
installed, maintained, or operated in accordance with furnished
written instructions, or has been altered or modified in any
way by any unauthorized person.

b. to any expenses, including labor or material, incurred during

removal or reinstallation of the Product

c. to any damage due to corrosion by chemicals, including

halogenated hydrocarbons, precipitated in the air

d. to any workmanship of the installer of the Product

3. This limited warranty is conditional upon:

a. advising the installing contractor, who in turn notify the

distributor or manufacturer

b. shipment to the Manufacturer of that part of the Product thought

to be defective. Goods can only be returned with prior written
approval of the Manufacturer. All returns must be freight
prepaid.

c. determination in the reasonable opinion of the Manufacturer

that there exists a defect in material or workmanship

4. Repair or replacement of any part under this Limited Warranty

shall not extend the duration of the warranty with respect to such
repaired or replaced part beyond the stated warranty period.

5

. THIS LIMITED WARRANTY IS IN LIEU OF ALL WARRANTIES,

EITHER EXPRESS OR IMPLIED, AND ALL SUCH OTHER
WARRANTIES, INCLUDING WITHOUT LIMITATION IMPLIED
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A
PARTICULAR PURPOSE, ARE HEREBY DISCLAIMED AND
EXCLUDED FROM THIS LIMITED WARRANTY.  IN NO EVENT
SHALL THE MANUFACTURER BE LIABLE IN ANY WAY FOR
ANY CONSEQUENTIAL, SPECIAL, OR INCIDENTAL DAMAGES
OF ANY NATURE WHATSOEVER, OR FOR ANY AMOUNTS
IN EXCESS OF THE SELLING PRICE OF THE PRODUCT OR
ANY PARTS THEREOF FOUND TO BE DEFECTIVE. THIS
LIMITED WARRANTY GIVES THE ORIGINAL OWNER OF THE
PRODUCT SPECIFIC LEGAL RIGHTS. YOU MAY ALSO HAVE
OTHER RIGHTS WHICH MAY VARY BY JURISDICTION.

In the interest of product improvement, we reserve the right to make changes without notice.

Содержание TUBULAR GAS FIRED PROPELLER UNIT HEATERS

Страница 1: ...that these substances may cause cancer birth defects or other reproductive harm INSTALLER S RESPONSIBILITY Installer Please Note This equipment has been test fired and inspected It has been shipped f...

Страница 2: ...6 Proper Clearances 5 6 Suspension of Units 5 6 Gas Piping 7 8 ELECTRICAL CONNECTIONS 9 10 11 12 13 VENTING 14 15 16 17 18 OPERATION Explanation of Controls and Operation 19 Main Burner Orifice Sched...

Страница 3: ...rocedures listed on Gas Equipment Start Up Sheet located in this manual Use only the fuel for which the heater is designed see rating plate Using LP gas in a heater that requires natural gas or vice v...

Страница 4: ...8 5 8 48 5 8 473 473 473 778 778 778 1235 1235 1235 F Discharge Opening Width 18 3 4 18 3 4 18 3 4 30 3 4 30 3 4 30 3 4 48 3 4 48 3 4 48 3 4 476 476 476 781 781 781 1238 1238 1238 G Depth to CL Flue 4...

Страница 5: ...epair Garages In Canada installation must be in accordance with current CGA B149 Installation Codes for Gas Burning Appliances and Equipment AIR DISTRIBUTION Direct air towards areas of maximum heat l...

Страница 6: ...acent materials Make certain that the lifting methods used to lift the heater and the method of suspension used in the field installation of the heater are capable of uniformly supporting the weight o...

Страница 7: ...ity Gas Nominal Iron Internal Length of Pipe Feet meters Pipe Size Dia 10 20 30 40 50 60 70 80 90 100 125 150 175 200 in in 3 0 6 1 9 1 12 2 15 2 18 3 21 3 24 4 27 4 30 5 38 1 45 7 53 3 61 0 1 2 0 622...

Страница 8: ...test edition National Fuel Gas Code in Canada according to CGA B149 See Tables 1 3 for correct gas piping size If gas pressure is excessive on natural gas applications install a pressure regulating va...

Страница 9: ...n cause severe personal injury or death Standard units are shipped for use on 115 volt 60 hertz single phase electric power The motor name plate and electrical rating of the transformer should be chec...

Страница 10: ...Units Equipped with Hot Surface Pilot Single Stage 100 400 Unit Sizes with Natural Gas and Propane LP Gas Figure 5d Primary HWSV9540 SV9640 Hot Surface Ignition Gas Controls Figure 5e Alternate HWSV95...

Страница 11: ...11 ELECTRICAL CONNECTIONS continued Figure 5f Tubular Units Equipped with S8600 Single Stage Ignition Optional for Tubular 100 400 Unit Sizes with Natural Gas and Propane LP Gas...

Страница 12: ...12 ELECTRICAL CONNECTIONS continued Figure 5g Tubular 100 400 Unit Sizes with Optional 2 Stage Ignition...

Страница 13: ...s in areas under negative pressure due to large exhaust fans or air conditioning When required a flue vent fan should be installed in accordance with the instructions included with the fan 10 Vent con...

Страница 14: ...hall terminate at least four feet 1 2m below four feet 1 2m horizontal from or one foot 0 3m above any door window or gravity vent air inlet into the building The vent terminal must be at least 12 inc...

Страница 15: ...l codes with current CGA B149 1 Installation Codes for Natural Gas Burning Appliances and Equipment or CGA B149 2 Installation Codes for Propane Gas Burning Appliances and Equipment 2 Any reference to...

Страница 16: ...16 Figure 8A Figure 8B VENTING continued...

Страница 17: ...17 VENTING continued Figure 9A Figure 9B...

Страница 18: ...wall thermostat supplied optionally is a temperature sensitive switch which operates the vent system and the ignition system to control the temperature of the space being heated It must be mounted on...

Страница 19: ...unit heaters must be orificed to 90 of the normal altitude rating and be so marked in accordance with CSA certification Check the gas input rate as follows Refer to General Safety Information section...

Страница 20: ...ssure altitude of the unit installation and the technician s name and date on the label using a permanent marker Refer to Installation Instruction section on Adjustments Gas Input Rate for adjusting t...

Страница 21: ...ssure Refer to Operation Replace regulator section of combination gas valve or complete valve Check with local gas supplier for proper orifice size and replace Refer to Operation 1 Clean main burner p...

Страница 22: ...ration 3 Purge air from gas line 4 Follow lighting instruction label adjacent to gas valve 5 Remove pilot orifice Clean with compressed air or solvent Do not ream 6 Refer to Operation 7 Check thermoco...

Страница 23: ...cal Connections 2 Replace motor 3 Check for 24V across 1 and 3 terminals on fan relay If 24V is present jumper terminals numbered 2 and 4 If motor runs the relay is defective and must be replaced If 2...

Страница 24: ...will be free from defects in material or workmanship for 1 year from the date of shipment from the factory or one and one half 1 1 2 years from the date of manufacture whichever occurs first The Manuf...

Страница 25: ...the heat exchanger 5 Remove any dirt dust or other foreign matter from the burners using a wire brush and or compressed air Ensure that all parts are unobstructed Inspect and clean the pilot burner i...

Страница 26: ...FICATION OF PARTS PROPELLER UNIT HEATERS Figure 13 Heat Exchanger Assembly Figure 14 Electrical Control Panel Figure 11 Propeller Parts Figure 12 Component Parts D4430 Fan Guard Fan Blade Hardware Har...

Страница 27: ...er Assembly 300 400 Unit Sizes Shown HOW TO ORDER REPLACEMENT PARTS Please send the following information to your local representative if further assistance is needed contact the manufacturer s custom...

Страница 28: ...and all the controls on this equipment If not contact your wholesaler or rep DO NOT START this equipment unless you fully understand the controls GAS EQUIPMENT START UP GENERAL With power and gas off...

Отзывы: