background image

  Table 5 - Main Burner Orifi ce Schedule*

 

PRIMARY AIR SHUTTER ADJUSTMENT

After the unit has been operating for at least 15 
minutes, adjust the primary air flow to the burners. 
Turn the friction-locked, manually-rotated air shutters 
clockwise to close, or counterclockwise to open (see 
Figures 11, 12, 14 and 16).

 For correct air adjustment, close 

the air shutter until yellow tips in the flame 
appear. Then open the air shutter to the point 
just beyond the position where yellow tipping 
disappears. Refer to Figure 12 .

NOTICE: There may be momentary and spasmodic 
orange flashes in the flame. This is caused by the 
burning of airborne dust particles, and not to be 
confused with the yellow tipping, which is a stable 
or permanent situation when there is insufficient 
primary air.

Figure 12 - Main Burner Flames

16

GAS INPUT RATE

Check the gas input rate as follows

 (Refer to general 

safety section for metric conversions/SI units):

 Never overfire the unit heater, 

as this may cause unsatisfactory operation or 
shorten the life of the heater.

1.  Turn off all gas appliances that use gas through the  
 

same meter as the unit heater.

2.  Turn gas on to the unit heater.
3.  Clock the time in seconds required to burn one 

cubic foot of gas by checking the gas meter.

4.  Insert the time required to burn one cubic foot of 

gas into the following formula and compute the 
input rate.

 

3600 (Sec. Per Hr.) x Btu/Cu. Ft

                                                             = Input Rate
                       Time (Sec.)

For example, assume the Btu content of one cubic foot 
of gas equalled 1000 and that it takes 18 seconds to 
burn one cubic foot of gas.

 

3600 x 1000

 

 

 

   = 200,000 Btu/Hr.

 

        18

NOTICE: If the computation exceeds or is less 
than 95 percent of the gas Btu/hr. input rating (see          
Specifi cations), adjust the gas pressure.

GAS PRESSURE ADJUSTMENTS

Adjust the gas pressure as follows:
1.  NATURAL GAS: Optimum results are obtained when 

the unit heater is operating at its full input rating with 
the manifold pressure of 3.5 inches  W.C. (0.9 kPa). 
Adjustment of the pressure regulator is not normally 
necessary since it is preset at the factory. However, 
fi eld adjustment may be made as follows:
(a.)  Attach manometer at pressure tap plug adjacent 

to the control outlet.

(b.) Remove regulator adjustment screw cap,  

located on combination gas valve.

(c.) With a small screwdriver, rotate the adjustment  

screw counterclockwise to decrease or clock-            
wise to increase pressure. Do not force beyond  
stop limits.

(d.) Replace regulator adjustment screw cap.

2.  PROPANE GAS: An exact manifold pressure of 10.0 

inches W.C. (2.5 kPa) must be maintained for proper 
operation of the unit heater. If the unit is equipped 
with a pressure regulator on the combination gas 
valve, follow steps “a” through “d” above. If the unit 
is not so equipped, the propane gas supply system 
pressure must be regulated to attain this manifold 
operating pressure.

3.  The adjusted manifold pressure should not vary 

more than 10% from the pressure specified in        
Table 5.

*

INPUT

IN 

1000

BTU

2500 BTU/Ft

3

(93.1 MJ/m

3

)

PROPANE

TYPE OF GAS

NATURAL

HEATING VALUE

1075 BTU/Ft

3

(40.1 MJ/m

3

)

3.5" W.C.

(0.87kPA)

1

0" W.C.

(2.49 kPA)

NO. OF

BURNER

ORIFICES

MANIFOLD

PRESSURE

* This schedule is for units operating at normal altitudes of 2000 ft. (610m) or 
less. SPECIAL ORIFICES ARE REQUIRED FOR INSTALLATIONS ABOVE 
2,000 FT. (610M).

When installed in Canada, any references to deration at altitudes in excess of 
2000 feet (610m) are to be ignored. At altitudes of 2000 to 4500 feet (610 to 
1372m), the unit heaters must be orifi ced to 90% of the normal altitude rating, 
and be so marked in accordance with the ETL certifi cation.

4

5

6

7

8

9

10

12

14

16

100

125

150

175

200

225

250

300

350

400

FT 

3

/HR

ORIFICE DRILL

FT 

3

/HR

ORIFICE DRILL

FT 

3

/HR

ORIFICE DRILL

FT 

3

/HR

ORIFICE DRILL

FT 

3

/HR

ORIFICE DRILL

FT 

3

/HR

ORIFICE DRILL

FT 

3

/HR

ORIFICE DRILL

FT 

3

/HR

ORIFICE DRILL

FT 

3

/HR

ORIFICE DRILL

FT 

3

/HR

ORIFICE DRILL

96
42

120

42

140

42

163

42

186

42

210

42

233

42

280

42

326

42

372

42

40
54
50
54
60
54
70
54
80
54
90
54

100

54

120

54

140

54

160

54

NORMAL

(HARD FLAME)

LIFTING

(TOO MUCH AIR)

YELLOW TIPPING

(MARGINAL)

YELLOW FLAME

(TOO LITTLE AIR)

Содержание QVEF 100 M

Страница 1: ...instructions to avoid exposure to fuel substances or substances from incomplete combustion which can cause death or serious illness The state of California has determined that these substances may ca...

Страница 2: ...have any questions after reading this manual contact the manufacturer See Identification of Parts Section for unit components Front View Rear View Indicates an imminently hazardous situation which if...

Страница 3: ...ied individual per instructions in this manual Also follow procedures listed on the Gas Equipment Start Up Sheet located in this manual 3 GENERAL SAFETY INFORMATION 1 foot 0 305 m 1 inch 25 4 mm 1 psi...

Страница 4: ...9 0 186 0 249 0 249 Motor Type SP SP PSC PSC PSC PSC PSC PSC PSC PSC R P M 1 050 1 050 1 140 1 140 1 140 1 140 1 140 1 140 1 140 1 140 Amps 115V 2 6 4 2 4 7 5 8 5 8 5 8 5 8 9 4 11 6 11 6 DIMENSIONAL D...

Страница 5: ...must not be installed in locations where air for combustion would contain chlorinated halogenated or acidic vapors If located in such an environment premature failure of the unit will occur Since the...

Страница 6: ...e between walls and the vertical sides of the Unit Heater shall be no less than 18 inches 457mm A minimum clearance of 6 inches 152mm must be maintained between the top of the Unit Heater and the ceil...

Страница 7: ...tiply the Cu Ft Hr Cubic Meters per Hour value by 0 633 then use the table 4 Refer to the metric conversion factors listed in General Safety section for more SI unit measurements conversions To avoid...

Страница 8: ...ing should be sized in accordance with the latest edition of ANSI Standard Z223 1 National Fuel Gas Code in Canada according to CSA B149 See Tables 1 and 3 for correct gas supply piping size If gas pr...

Страница 9: ...ersonal injury or death Standard units are shipped for use on 115 volt 60 hertz single phase electric power The motor nameplate and electrical rating on the transformer should be checked before energi...

Страница 10: ...regarding these venting conditions CARBON MONOXIDE Your venting system must not be blocked by any snow snow drifts or any foreign matter Inspect your venting system to ensure adequate ventilation exi...

Страница 11: ...llow this procedure 1 Hold power venter motor in position 2 Remove the three Phillips head screws from the motor adaptor plate 3 Remove the three screws which connect the power venter stack to the pow...

Страница 12: ...12 Figure 10A VENTING continued Figure 10B...

Страница 13: ...13 Figure 10C VENTING continued Figure 10D...

Страница 14: ...isting of a power venter motor and blower pressure switch and sealed flue collector in place of the conventional draft diverter The addition of external draft hoods or power ventors is not permitted A...

Страница 15: ...ywell Pilot Burner 13 High Limit This safety device is located on the rear header plate of the heat exchanger air inlet side 15 13 Figure 11 Burner Components Intermittent Pilot Ignition Also refer to...

Страница 16: ...C 0 9 kPa Adjustment of the pressure regulator is not normally necessary since it is preset at the factory However field adjustment may be made as follows a Attach manometer at pressure tap plug adja...

Страница 17: ...e minimum clearance requirements listed in this manual Under no circumstances should combustible material be located within the clearances specified in this manual Failure to provide proper clearance...

Страница 18: ...efer to Installation 7 Refer to Installation 1 Open all manual gas valves 2 Replace fuse or turn on power supply 3 Turn up thermostat 4 Check limit switch with continuity tester If open replace limit...

Страница 19: ...Do not ream 6 Refer to Operation 7 Check thermocouple connection and replace if defective 8 Eliminate drafts Refer to Installation 9 Inspect and correct all wiring 10 Inspect and correct ignition sys...

Страница 20: ...or short such as staples piercing thermostat wiring and correct Replace gas valve Refer to Operation 1 Be sure fan switch heater terminals are connected per diagrams 1 Refer to Operation 2 Check motor...

Страница 21: ...valve if not replace S8600 Igniter 1 Lengthen vertical run of flue pipe see venting 2 Burner orifice may be too large verify replace if req d 3 Increase air flow check fan size Check for proper voltag...

Страница 22: ...ROPELLER UNIT HEATERS Figure 13 Propeller Parts 1 HEAT EXCHANGER 2 FLUE COLLECTOR 3 BURNER DRAWER Figure 15 Internal Furnace Components Figure 16 Burner Assy Parts 115 1 60 MOTOR FAN GUARD FAN BLADE H...

Страница 23: ...400 units 6 dia flue outlet Increaser required To be supplied by manufacturer 23 REF NO DESCRIPTION 1 Blower Housing Assembly 2 Speed Nut 3 Motor 4 Washer Plain 5 Plate Adapter 6 Blower Wheel 7 Mounti...

Страница 24: ...rews Item 12 Do not loose these parts Using caution the motor will disengage from the Mounting Adapter Plate along with the Relay Junction Box and Pressure Switch Mounting Brackets will also disengage...

Страница 25: ...instructions or has been altered or modified in any way by any unauthorized person b to any expenses including labor or material incurred during removal or reinstallation of the Product c to any damag...

Страница 26: ...NOTES 26...

Страница 27: ...een installed Do you understand all the controls on this equipment If not contact your wholesaler or rep DO NOT START this equipment unless you fully understand the controls GAS EQUIPMENT START UP GEN...

Страница 28: ......

Отзывы: